turck IME-AIA-11Ex-Hi/24VDC Quick Start Manual Download Page 1

Isolating Transducer 
IME-AIA-11Ex-Hi/24VDC 
 

Short description

•  Intrinsically safe powering of  

 

 

transmitters and isolated transmission 

 

of analog signals

•  Input 4…20 mA
•  Output 4…20 mA, short-circuit protected
•  Galvanic isolation between input and    
 output 
•  Intrinsically safe input circuit Ex ia  

 

•  Application area according to 
    ATEX: II (1) GD, II 3 G
•  Approved for installation in zone 2 
• HART

®

 communication 

•  Transmission characteristic 1:1 

Terminal confi guration 

(Fig. 2)

3, 4      Intrinsically safe input circuit 4...20 mA
10, 9     Output circuit 4...20 mA
14, 13   Power supply
 12, 11   Power supply looped in

Connection via cage-clamp terminals:
Connection profi le 0,75 mm

2

…1,5 mm

2

 blank 

wire, 0,5 mm

2

…1 mm

2

 with wire sleeves.

LED indications 

(Fig. 1 + 2)

Pwr  

green 

 power 

on

 

Functions

Galvanically isolated connection of measuring 
two wire transducers by meaning of standard 
analog signals 0/4…20 mA from hazardous 
area into safe area.

Special conditions for application in zone 2

For installation in zone 2 the device must be 
installed in a housing which complies with the 
requirements of EN 60079-15 with a minimum 
protection degree of IP54 according to 
IEC/EN 60529. 

With mounting in zone 2 the connecting and 
disconnecting of energized non energy limited 
circuits is only permitted in non-explosive 
atmosphere. 

The application of litz-wires recommends the 
fi xation of cable ends with wire sleeves.

Mounting and Installation 

(Fig. 4 + 5)

 

The device is suited for snap-on clamps for 
DIN rail mounting (EN 60715). 

Devices of the same type may be mounted 
directly next to each other. It must be ensured 
that heat is conducted away from the device. 
Mounting and installation must be carried out in 
accordance with the applicable regulations. 
The operator is responsible for compliance with 
the regulations.

The device must be protected against dust, 
dirt, moisture and other environmental infl u-
ences as well as against strong electromagnetic 
emissions. 
It should also be protected against the risks of 
mechanical damaging, unauthorized access 
and incidental contact. 

All installations must be carried out observing 
the regulations of EMC protection.

The cable junction via cage-clamp terminals is 
shown in Fig. 4.

 

Fig. 1   Front view

 

Fig. 2   Circuit diagram 

 

Fig. 4  Cable junction

Fig. 5  Dimension drawing

IME-AIA-11Ex-Hi

24VDC

Pwr

4…20 mA

9, 11, 13 –

10 +

– 4

+ 3

4...20 mA

?

12, 14 +

HART

®

GN

Pwr

24 VDC

112

18

110