background image

Your Global Automation Partner

Instructions for Use

IM18-CCM50…

Cabinet Guard

Summary of Contents for IM18-CCM50 Series

Page 1: ...Your Global Automation Partner Instructions for Use IM18 CCM50 Cabinet Guard...

Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Page 3: ...em partitions and recovery system 9 4 4 2 Ethernet interfaces 9 4 4 3 CAN RS485 interface 9 4 4 4 GPIOs 9 4 4 5 Analog inputs 10 4 4 6 Relay 10 4 4 7 Trusted Platform Module Controller TPM controller...

Page 4: ...rtition 23 9 3 Enable USB device 23 10 Troubleshooting 24 10 1 Recovery system 24 11 Maintenance 25 11 1 Carrying out a firmware update via the console 25 11 2 Transferring the firmware update via Win...

Page 5: ...us situation with medium risk of death or severe in jury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may result in minor or moderate injury if not avoided NOTIC...

Page 6: ...t for attaching reflective surfaces 2 3 Legal requirements The device is subject to the following EC directives n 2014 30 EU electromagnetic compatibility n 2011 65 EU RoHS Directive 2 4 Turck service...

Page 7: ...y only be used as described in these instructions Any other use is not in accord ance with the intended use Turck accepts no liability for any resulting damage 3 2 Obvious misuse n The device is not a...

Page 8: ...distance sensor as well as a temperature and humidity sensor The Linux Debian operating system is preinstalled on the device The device functions must be programmed as required 4 1 Device overview RS...

Page 9: ...revert to the pre vious executable system A recovery system is started in the event that both system partitions fail The recovery system resets the device to the factory settings 4 4 2 Ethernet inter...

Page 10: ...he relay output Simple shell scripts are provided on the system as sup port for the configuration 4 4 7 Trusted Platform Module Controller TPM controller The device is provided with a trusted platform...

Page 11: ...evice can be mounted on a DIN rail according to EN 60715 TH35 The minimum clear ance from other devices must be at least 15 mm RS485 CAN ETH0 Pwr Com Err IM18 CCM 10 11 12 7 8 9 4 5 6 1 2 3 RS485 CAN...

Page 12: ...ting an external sensor The CAN RS485 interface is implemented as an RJ45 socket The maximum cable length is 30 m Connect the external sensor to the device via the CAN RS485 interface 87654321 v 1 CAN...

Page 13: ...lity to use sudo options Command example This_is_a_console command example path Example output Example content of a file 7 1 Establishing a network connection After a physical connection has been esta...

Page 14: ...952 0 F 49 208 4952 264 more turck com www turck com Fig 7 Access via PuTTY After the login the folder home in the working directory becomes active with restricted write access rights Write and read o...

Page 15: ...V01 01 2021 09 15 Fig 8 Login output...

Page 16: ...operating system and user software Install the package sudo apt update sudo apt install PACKAGE The device has the following partitions Mount point Size Contents 1 4 GB System partition var 256 MB Va...

Page 17: ...10 Output of the help texts for scripts The following table is an overview of the scripts present in the IM18 CCM Function Script Option Description Ambient temperat ure and air humid ity ambient_rea...

Page 18: ...20mA channel 1 or 2 help Display help text analog_read sh 1 Measurement of the analog value on channel 1 2 Measurement of the analog value on channel 2 help Display help text GPIO gpio_init sh pin in...

Page 19: ...d correspond ing periphery 8 2 Linux system paths and interfaces overview The following table shows an overview of the most important system devices and system paths as well as interfaces under Linux...

Page 20: ...Set level when configured as output low or high gpio66 Digital output GPIO1 Read level at GPIO1 irrespective of configura tion gpio103 Digital output GPIO1 Diagnostic signal low output inactive or er...

Page 21: ...0 20 mA Direction Output level high Direction Output level low Direction Output level low 8 4 Analog inputs available modes and configurations GPIO con figura tion Level P gpio Switching between input...

Page 22: ...Hz Device is operational Com Green Communication active Err Red Error indication 9 1 1 Programming LED indication The LEDs can be programmed as required via the operating system The following table sh...

Page 23: ...t devices 11 block id 0424 2440 serial 000000225001 name Ultra Fast Media hash IshTzwLfa a The identification number by which the USB device is activated appears at the beginning of the line here 11 E...

Page 24: ...or an update fails the partitions make it possible to revert to the pre vious executable system or recovery system The active system is marked as faulty after three failed boot operations in successi...

Page 25: ...a suitable tool e g WinSCP or FileZilla or as a secure copy Load the update file e g IM18 CCM30 MTI 24VDC_V1 0 2 raucb via a suitable tool e g WinSCP to the device Alternatively Transfer the update f...

Page 26: ...ls Requirements n WinSCP is installed n PuTTY is installed n The update file is available as a raucb file on a local computer Transferring a firmware file with WinSCP Log into the device in WinSCP wit...

Page 27: ...V01 01 2021 09 27 Navigate in WinSCP to the memory location of the update file on the host PC Fig 13 WinSCP memory location of the firmware file on the host PC...

Page 28: ...aintenance 28 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com Navigate to the directory home update on the device Fig 14 WinSCP directory home update on the device...

Page 29: ...e directory home update by drag and drop or by clicking Upload Fig 15 Directory home update Confirm with OK a The transfer of the update file is displayed by WinSCP as follows Fig 16 WinSCP file trans...

Page 30: ...via Load for later repetitions Open PuTTY Enter the following settings in PuTTY n Host Name Name or IP address of the device in this case 192 168 1 20 n Port 1522 Optional Assign a name for the curre...

Page 31: ...Your File file raucb succeeded is displayed Restart the device with the command sudo reboot Fig 19 PuTTY restarting the device Check the current firmware status e g read out directly from the partiti...

Page 32: ...with a Decontamination declaration enclosed The decontamination declaration can be downloaded from https www turck de en retoure service 6079 php and must be completely filled in and affixed securely...

Page 33: ...PIO outputs Number 2 Voltage drop to UB UB 1 6 V at 100 mA UB 2 5 V at 200 mA Output current 200 mA Output type Push pull Short circuit proof no potential isolation Analog current input Measuring rang...

Page 34: ...C Relative humidity 10 90 internal no condensation at 45 C storage Installation height 2000 m above sea level Type of protection IP20 Housing material Polycarbonate ABS Dimensions 125 mm 110 mm 18 mm...

Page 35: ...MARNE LA VALLEE Cedex 4 www turckbanner fr Great Britain TURCK BANNER LIMITED Blenheim House Hurricane Way GB SS11 8YT Wickford Essex www turckbanner co uk India TURCK India Automation Pvt Ltd 401 40...

Page 36: ...RCK RUS OOO 2 nd Pryadilnaya Street 1 105037 Moscow www turck ru Sweden Turck Sweden Office Fabriksstr ket 9 433 76 Jonsered www turck se Singapore TURCK BANNER Singapore Pte Ltd 25 International Busi...

Page 37: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100023796 2021 09 100023796...