Flow monitoring
Immersion sensor without integrated processor
FCS-GL1/2A4-NAEX0-H1141
Edition
•
2015-10-24T20:22:01+02:00
1 / 2
Hans Turck GmbH & Co.KG
ñ
D-45472 Mülheim an der Ruhr
ñ
Witzlebenstraße 7
ñ
Tel. 0208 4952-0
ñ
Fax 0208 4952-264
ñ
ñ
www.turck.com
Type code
FCS-GL1/2A4-NAEX0-H1141
Ident no.
6870470
Mounting conditions
insertion style sensor
Water Operating Range
1…100cm/s
Oil Operating Range
3…200 cm/s
Stand-by time
typ. 8 s (2…18 s)
Switch-on time
typ. 2 s (1…13 s)
Switch-off time
typ. 2 s (1…15 s)
Temperature jump, response time
max. 12 s
Temperature gradient
ð
250 K/min
Medium temperature
-20…60 °C
Device designation
É
II 1/2 G EEx ia IIC T6
ignition protection category
Ex ia IIC
PowerP
i
ð
0.69 W
Internal inductances/capacitances
negligibly small
Ex approval acc. to conformity certificate
TÜV 99 ATEX 1517X
IP Rating
IP67
Housing material
stainless steel, V4A (1.4571)
Sensor material
stainless steel, AISI 316Ti
Max. tightening torque housing nut
100 Nm
Connection
male, M12 x 1
Pressure resistance
60 bar
Process connection
G ½″ long
■
ATEX category II 1/2 G, Ex zone 0
■
Intrinsically safe flow sensor for liquid
media
■
Calorimetric principle
■
Adjustment via potentiometer at Ex sig-
nal processor
■
Status indicated via LED chain on sig-
nal processor
■
Intrinsically safe EEx ia IIC T6, for use
in zone 0
■
Plug-in device, M12 x 1
■
4-wire connection to an Ex0 processor
Wiring diagram
Functional principle
Our insertion - flow sensors operate on the
principle of thermodynamics. The measur-
ing probe is heated by several °C as against
the flow medium. When fluid moves along the
probe, the heat generated in the probe is dis-
sipated. The resulting temperature is mea-
sured and compared to the medium tempera-
ture. The flow status of every medium can be
derived from the evaluated temperature differ-
ence. Thus TURCK's wear-free flow sensors
reliably monitor the flow of gaseous and liquid
media.