Technical features
D301239 1013 - BL67 AIDA PROFINET
4-30
Analog combi modules
BL67-2AI2AO-V/I
(4 byte per channel)
–
channel 0 = bit 0 - 3
–
channel 1 = bit 4 - 7
Table 4-22:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
Inputs
0/4
0 to 3
Operation mode
00 00 = voltage, -10 ... 10 VDC standard
A
0001 = voltage, 0 ... 10 VDC standard
0010 = voltage,-10 ... 10 VDC PA (NE 43)
0011 = voltage, 0 ... 10 VDC PA (NE 43)
0100 = voltage, -10 ... 10 VDC ext. range
0101 = voltage, 0 ... 10 VDC ext. range
0110 = reserved
0111 = reserved
1000 = 0 ... 20 mA Standard
1001 = 4 ... 20 mA Standard
1010 = 0 ... 20 mA PA (NE 43)
1011 = 4 ... 20 mA PA (NE 43)
1100 = 0 ... 20 mA ext. range
1101 = 4 ... 20 mA ext. range
1111 = deactivate
4
Value representation
0 = Integer (15 bit + sign)
A
1 = 12 bit (left-justified)
5
Diagnosis
0 = release
1 = block