D301239 1013 - BL67 AIDA PROFINET
4-27
Parameterization
Analog output modules
BL67-2AO-I
BL67-2AO-V
Table 4-17:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0
0
current mode
0 = 0...20 mA
A
1 = 4...20 mA
1
Value representation
0 = Integer (15 bit + sign)
A
1 = 12 bit (left-justified)
2
reserved
3 Channel
0
=
activate
A
1 = deactivate
4 to 7
reserved
1
Substitute value
Low byte
In Modbus, it is not possible the give out a
substitute value in case of an error, see also
.
2
Substitute value
High byte
Table 4-18:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0
0
voltage mode
0 = 0...10 V
A
1 = -10...+10 V
1
Value representation
0 = Integer (15 bit + sign)
A
1 = 12 bit (left-justified)
2
reserved
3 Channel
0
=
activate
A
1 = deactivate
4 to 7
reserved
1
Substitute value
Low byte
2
Substitute value
High byte