Technical features
D301239 1013 - BL67 AIDA PROFINET
4-26
Digital output modules
BL67-16DO-0.1A-P
Table 4-16:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0
0
Open circuit current LSB
(channel 0 to 7)
0 to 12
A
– current below which an open circuit
diagnosis is generated: "Value" × 10 mA
1 + 2
reserved
3
Open circuit current MSB
(channel 8 to 15)
0 to 12
A
– current below which an open circuit
diagnosis is generated: "Value" × 10 mA
4
Short-circuit current LSB
(channel 0 to 7)
0
A
to 12
– current above which a short-circuit
diagnosis is generated: "Value" × 10 mA
5 + 6
reserved
7
Short-circuit current MSB
(channel 8 to 15)
0
A
to 12
– current above which a short-circuit
diagnosis is generated: "Value" × 10 mA
1
0
DiaOverCur
0 = short-circuit diagnosis off
1 = short-circuit diagnosis on
A
1
DiaOpeLoa
0 = open circuit diagnosis off
A
1 = open circuit diagnosis on
2 to 7
reserved
Summary of Contents for BL67-GW-PN-AC