Technical features
D301239 1013 - BL67 AIDA PROFINET
4-22
Analog input modules
BL67-2AI-I
(1 byte parameters per channel)
BL67-2AI-V
(1 byte parameters per channel)
Table 4-10:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0/1
0
current mode
0 = 0...20 mA
A
1 = 4...20 mA
1
Value representation
0 = Integer (15 bit + sign)
A
1 = 12 bit (left-justified)
2 Diagnosis
0
=
activate
A
1 = deactivate
3 Channel
0
=
activate
A
1 = deactivate
Table 4-11:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0/1
0
voltage mode
0 = 0...10 V
A
1 = -10...+10 V
1
Value representation
0 = Integer (15 bit + sign)
A
1 = 12 bit (left-justified)
2 Diagnosis
0
=
activate
A
1 = deactivate
3 Channel
0
=
activate
A
1 = deactivate