D301239 1013 - BL67 AIDA PROFINET
4-13
Diagnosis in PROFINET
4.10
Diagnosis in PROFINET
In PROFINET, critical events (diagnostic messages) are reported acyclically as alarms.
In addition to information as slot-number, subslot-number, channel type etc., the diagnostic telegrams
contain error codes which define the diagnostic event more precisely.
The error codes are interpreted by the PLC-software or respective function block, so that the diagnostic
messages are normally displayed as plain text.
You will find an example of a diagnostic telegram in
, under
.
Please read the following sections, for the meaning of the error codes of the BL67-gateway and the
I/O-modules.
4.10.1
Gateway Error codes
Table 4-4:
gateway
error codes
Value (dec.)
Diagnostics meaning for the gateway
Error codes (1 to 9 according to the standards)
2
Undervoltage:
Undervoltage channel 0: Undervoltage at (US1) U
SYS
Undervoltage channel 1: Undervoltage at (US2) U
L
Error codes (16 to 31 manufacturer specific)
16
Parametrization error/ configuration error
–
Station configuration changed
→
The configuration is currently deviating from the reference list of modules.
Process data can still be exchanged with the module bus stations which are at
present connected to the module bus. The constellation of the module bus station
that is set in the configuration software of the corresponding controller serves as a
reference.
– Master configuration error
→
Display: Configuration error/ parameterization error at
channel 1
→
The actual list of modules has been altered in such a manner, that no process data
can be exchanged with the module bus stations which are at present connected to
the module bus.
– Station configuration error
→
Display: Configuration error/ parameterization error at
channel 0
→
The gateway could not prepare the station’s configuration to be read out.
22
Behavior at communication loss
–
Module bus error
→
Communication with the module bus station on the module bus is not possible.
Summary of Contents for BL67-GW-PN-AC
Page 1: ...USER MANUAL PROFINET AIDA gateway BL67 GW PN AC...
Page 6: ...D301239 1013 BL67 AIDA PROFINET iv...
Page 20: ...PROFINET D301239 1013 BL67 AIDA PROFINET 3 4...
Page 66: ...Technical features D301239 1013 BL67 AIDA PROFINET 4 46...
Page 94: ...Guidelines for station planning D301239 1013 BL67 AIDA PROFINET 6 6...
Page 112: ...Mounting and mounting instructions D301239 1013 BL67 AIDA PROFINET 8 10...
Page 116: ...Appendix D301239 1013 BL67 AIDA PROFINET 9 4...