D301239 1013 - BL67 AIDA PROFINET
8-3
Building up a BL67 station
8.2
Building up a BL67 station
8.2.1
Mounting a gateway
The gateway is the head of a BL67-station.
The electronic modules are mounted on the right side of the gateway.
8.2.2
Mounting a base module
1
The module bus contacts of the first base module have to be inserted from above into the module
bus contacts of the gateway.
2
Tighten the screws of the inserted base module.
3
All other base modules of the station are mounted identically. Their module bus contacts have to
fit into the contacts of the respective left-hand base module.
Note
The BL67-station should be assembled completely before mounting it on a mounting plate or
a mounting rail.
Attention
To guarantee the protection class IP67, the screws at the base modules have to be firmly
tightened.
Furthermore the seals at the left module bus contacts of the base modules must not be
damaged or slipped due to wrong transport, storage or similar.