Electromagnetic Compatibility (EMC)
7.3.6
EMC Compliant Cabinet Installation
A
Bonding straps
Bonding straps connect inactive metal components, if it is not possible to create a large surface area contact. Use
short bonding straps with large surface areas.
B
Mounting plates
Mounting plates used to hold control components must have a large surface area contact with the cabinet housing.
C
Protective conductor rail
The protective conductor rail must also be connected over a large surface area to the mounting plates and
additionally with an external cable (cross-section at least 10 mm2 / 0,015 inch2) to the protective conductor system to
avoid interference currents.
D
Protective conductor terminal block
The protective conductor terminal block must be connected to the protective conductor rail.
E
Protective conductor system cable (grounding point)
The cable must be connected over a large surface area with the protective conductor system.
Figure 7-4:
EMC compliant
cabinet installa-
tion
a
b
c
d
e
A
B
C
D
E
Summary of Contents for BL20-GW-CANOPEN
Page 1: ...BL20 USER MANUAL FOR CANopen...
Page 4: ......
Page 8: ...D301087 1211 BL20 CANopen iv...
Page 14: ...About this Manual D301087 1211 BL20 CANopen 1 6...
Page 24: ...BL20 Philosophy D301087 1211 BL20 CANopen 2 10...
Page 54: ...BL20 Communication in CANopen D301087 1211 BL20 CANopen 5 2...
Page 68: ...Guidelines for Station Planning D301087 1211 BL20 CANopen 6 14...
Page 82: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 2...
Page 83: ...D301087 1211 BL20 CANopen 8 3...
Page 84: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 4...
Page 85: ...D301087 1211 BL20 CANopen 8 5...
Page 86: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 6...
Page 92: ...Glossary D301087 1211 BL20 CANopen 9 6...