D301087 1211 - BL20 CANopen
4-5
Technical Data
4.4
Technical Data
4.4.1
General Technical Data
Relating to a Station
Note
The auxiliary power supply must comply with the stipulations of SELV (Safety Extra Low
Voltage) according to IEC 364-4-41.
Table 4-1:
General technical
data (station)
Supply voltage/ auxiliary voltage
Nominal value (provision for other modules)
24 V DC
Permissible range
according to EN 61131-2 (18 to 30 V DC)
Residual ripple
according to EN 61131-2
Potential isolation
Yes, via optocoupler
Ambient conditions
Ambient temperature
– T
Ambient
0 to +55 °C / 32 to 131 °F
– T
Store
-25 to +85 °C / 13 to 185 °F
Relative humidity
according to IEC 61 131-2/ EN 50 178
Climatic tests
according to IEC 61131-2
Noxious gas
– SO
2
:
10 ppm (rel. humidity < 75 %, non-condensing)
– H
2
S:
1.0 ppm (rel. humidity < 75 %, non-condensing)
Resistance to vibration according to IEC 61131-2
10 to 57 Hz, Constant
amplitude 0.075 mm / 0.003 inch, 1g
Yes
57 to 150 Hz, Constant acceleration 1 g
Yes
Mode of vibration
Frequency sweeps with a change in speed of
1 Octave/min
Period of oscillation
20 frequency sweeps per axis of coordinate
Shock resistant according to IEC 68-2-27
18 shocks, sinusoidal half-wave 15 g peak value/
11 ms, in each case in +/- direction per space
coordinate
Resistance to repetitive shock according to
IEC 68-2-29
1 000 shocks, half-sinus 25 g peak value/6 ms, in
each case in +/- direction per space coordinate
Topple and fall according to IEC 68-2-31 and free fall according to IEC 68-2-32
Weight
< 10 kg
Summary of Contents for BL20-GW-CANOPEN
Page 1: ...BL20 USER MANUAL FOR CANopen...
Page 4: ......
Page 8: ...D301087 1211 BL20 CANopen iv...
Page 14: ...About this Manual D301087 1211 BL20 CANopen 1 6...
Page 24: ...BL20 Philosophy D301087 1211 BL20 CANopen 2 10...
Page 54: ...BL20 Communication in CANopen D301087 1211 BL20 CANopen 5 2...
Page 68: ...Guidelines for Station Planning D301087 1211 BL20 CANopen 6 14...
Page 82: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 2...
Page 83: ...D301087 1211 BL20 CANopen 8 3...
Page 84: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 4...
Page 85: ...D301087 1211 BL20 CANopen 8 5...
Page 86: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 6...
Page 92: ...Glossary D301087 1211 BL20 CANopen 9 6...