Operation Instructions
6.3
Parameterization
The user must select the parameters suitable for its safety application.
6.3.1
Parameters
The parameters are set using the switches on the housing side.
This is done with the help of a screwdriver.
If the teach button is pressed for 3 s, the parameters are adopted.
Sensor type
Selection
Description
NAMUR
NAMUR sensor according to EN 60947-5-6
– 0-signal: sensor not actuated
– 1-signal: sensor actuated
Switch
Potential free contact
– 0-signal: switch open
– 1-signal: switch closed
Voltage signal
Voltage signal:
– 0-signal 0…3 V
– 1-signal 5…30 V
3-wire PNP
3-wire sensor (positive, negative, positive)
– 0-signal: sensor not actuated (0 V)
– 1-signal: sensor actuated (12 V)
3-wire NPN
3-wire sensor (negative, positive, negative)
– 0-signal: sensor not actuated (12 V)
– 1-signal: sensor actuated (0 V)
Line monitoring (for NAMUR-sensors):
Selection
Description
Off
Line monitoring is switched off
Wire break and short circuit
Line monitoring short circuit and wire break
Parameters:
Switch
Parameter
State
Comment
S1
Line monitoring
OFF/ON
OFF/ON
S2
Relay mode
2P/4P
(2-point)/(4-point)
S3
2P: Under/Overspeed
Under/Over
Under-/Overspeed
S4
Relay diretion
Ninv/inv
(not inverted)/(inverted)
S5
Function Relay Loc
OFF/ON
OFF/ON
S6
Locked switching
LocOn/Locoff
Locked On/Locked Off
S7
SUD Input
[E2]/[E3]
Input [E2]/input [E2]
S8
SUD mode
Dyn/Stat
Dynamic/Static