Mount the ducts. If mounted on the facade, there must be a descending gradient of 1-2%
toward the outside to avoid penetration of heavy rainwater into the unit.
Mount the outside facade grates. Mount the grate of the air exhaust with the lamellas
facing sideways. The sideways direction should be oriented in the direction away from the
air supply. Mount the grate of the air supply with the lamellas facing downwards.
Connect the power supply according to the included electrical diagram.
Note!
It is important to seal the ducts 100% at the spigot of the unit; otherwise
false air will penetrate the unit.
The ducts must on no account be twisted or pressed against the installation
collars of the unit, as it will cause an increased noise level of up to +6dB. Be
sure that the duct holes leave enough room for insulation with rockwool or
insulation foam.