TTL air curtain systems - Controller TWICS
9. Displays and basic operation settings (cont.)
9.5 Menu 3 - Basic settings
1-1000
Overrun time
1 SELECT PARAMETER
0180
3 Basic settings menu 1
Overrun time
Time of overrun within the AUTOMATIC mode operation
after shut-off of automatic contact (closing of door)
1-5
Heating stage
2 SELECT PARAMETER
1
3 Basic settings menu 2
Heating stage
Setting of operating stage to proceed in a HEATING mode
with a connected room thermostat (RT) after closing the door
0=NO
Aut . start after frost
3 SELECT PARAMETER
1
1=YES
3 Basic settings menu 3
Aut.start after frost
5HVWDUWDIWHUWULJJHULQJDIURVWDOHUWLI1(,112DFRQÀUPLQJ
is required by a renewed switch-on of the air curtain device
0=NO
DDC enable GLOBAL
4 SELECT PARAMETER
1
1=YES
3 Basic settings menu 4
DDC enable GLOBAL
Effect of an enable BMS signal for the unit directly contacted
at clambs 16/17 at the internal connection board (PCB)
or for all (GLOBAL) air curtain units in a bus group
0=NO
DDC enable MAN.MODE
5 SELECT PARAMETER
1
1=YES
3 Basic settings menu 5
DDC enable MAN.MODE
Effect of an enable BMS signal for HAND mode
0=NO
WINTER mode 26-27
6 SELECT PARAMETER
0
1=YES
3 Basic settings menu 6
WINTER mode 26-27
BMS signal at clambs 26-27 of the internal connecting board
(PCB) for SUMMER/WINTER switch over will be regarded