background image

2

Quick Start 

Guide

 

FG-SYS 

Digital

Panel

Guide de 
démarrage 
rapide 
de la centrale
FG-SYS

TIP: The complete installation notice for this product can be downloaded on TTK’s website by scanning the QR code. 
For more information, go to www.ttkuk.com; www.ttkusa.com; www.ttkasia.com

Astuce: Le manuel d’installation complète de ce produit peut être téléchargé sur le site Web de TTK en scannant le code QR. 
Pour plus d’informations, www.ttk.fr; www.ttkcanada.com

Power Supply: 100-240 V AC - 0.35 A - 50/60 Hz 
- Max. Consumption: 15W 
- Power Thermal Fuse 2 x 0.5 A on the secondary 
- Rating: Class 2 not inherent limited 
To avoid electromagnetic disturbances and emissions (EMC), the shielding of the 
leader cable must be connected to the earth. Using a metal cable clamp, fix the 
shielding of the leader cable (available at the back);

It is advisable to protect the digital electrically unit with a circuit breaker from 
0.5 A.   

     

IMPORTANT: To connect the grounding of the box to earth:
Use a standardized single-core 14 AWG (2.5 mm²) earth wire. 

Electrical Connection

Raccordement Electrique

EN

Alimentation électrique 100-240Vca - 0,35A - 50/60 Hz 
- Consommation max. : 15W 
- Thermal Power Fuse 2x0,5 A sur le secondaire
- Note: Classe 2 pas limitée inhérente

Pour respecter les normes de compatibilité électromagnétiques, il est 
absolument nécessaire de connecter l’arrière de la face avant à la terre ; le serre 
câble et la vis n°3, avec le sigle « Terre », est disponible à cet effet. 

Il est nécessaire de protéger électriquement la centrale avec un disjoncteur de 
0,5 A.

IMPERATIF : Raccorder la masse du boîtier à la terre :
Utiliser un fil de terre monobrin 2,5 mm² normalisé.

FR

1

   

Affix the digital panel to the wall, taking care not to damage the motherboard. Use 
the accurate template included in the FG-SYS F box, in order to affix the digital 
unit to the wall. 

  

We recommend fixing at a height between 5 ft (1.50m) and 6 ft (1.80m) , to provide 

a comfortable height for viewing the touch-screen display. 

Mounting the FG-SYS Digital Panel

Fixation de la Centrale de Détection FG-SYS

EN

FR

    Fixer la centrale au mur en prenant soin de ne pas endommager la carte mère. 

Un pochoir est fourni pour le perçage des 4 trous de fixation. 

   Nous recommandons une fixation à une hauteur comprise entre 1,50m et 1,80m 

pour permettre une lecture confortable de l’afficheur.

3

Connecting the Detection Circuits

Raccordement Circuits de Détection

Connect the 2 pairs of TTK BUS 8723 standard cable in each circuit, respecting 
the color code below:

A : Green wire, B : White wire, C : Black wire, D : Red wire

Plug each jumper cable into the cable clamp provided. Fix the shielding tightly to 
the cable clamp to ensure proper grounding. 

A and B in the unused circuit must be shunted.

EN

FR

Connecter les 2 paires de câbles bus TTK 8723 de chaque circuit, en respectant 
le code couleur ci-dessous : 

A : Fil Vert, B : Fil Blanc, C : Fil Noir, D : Fil Rouge

Brancher chaque câble de raccordement dans le serre-câble fourni. Fixer 
fermement l’écran (blindage) au serre-câble pour assurer une bonne mise à la 
terre.  

Dans le cas de circuit(s) non utilisé(s), laisser en place le shunt entre A et B sur 
le connecteur embrochable correspondant. 

6.3’

7.28’

4.2’

5.12’

Reviews: