25
Object
Corresponding Pins
Requirement
DRM0
5 & 6
The inverter is on standby mode
DRM1
1 & 6
The inverter is not consuming power
DRM2
2 & 6
The inverter is consuming less than 50% of rated power
DRM3
3 & 6
The inverter is consuming less than 75% of rated power AND
source reactive power if capable
DRM4
4 & 6
The inverter is consuming 100% of rated power (Subject to
constrains from other active DRMs)
DRM5
1 & 5
The inverter is not generating power
DRM6
2 & 5
The inverter is generating less than 50% of the rated power
DRM7
3 & 5
The inverter is generating less than 75% of the rated power AND
sink reactive power if capable
DRM8
4 & 5
The inverter is generating 100% of rated power (Subject to
constrains from other active DRMs)
5.6 CT/Meter Installation
Different solutions are offered for sampling data from PV and Grid side. The standard
solution is CT solution and the optional solution is Meter solutions. Please choose to use
one of the solutions to realize the sampling function.
5.6.1 CT Solution
Two CT offered, one is PV_CT and the other one is Grid_CT.
If choose CT solution, please install CTs with instructions as below:
Note
!
Please do not use the CT (standard solution) and meters (optional
solution) in a same system, otherwise the system will run abnormally.