![TSI Instruments SUREFLOW 8682 Operation And Service Manual Download Page 95](http://html1.mh-extra.com/html/tsi-instruments/sureflow-8682/sureflow-8682_operation-and-service-manual_1178123095.webp)
89
Appendix C
Wiring Information
Back Panel Wiring
PIN #
Input / Output /
Communication
Description
DIM
1, 2 Input
24 VAC to power Digital Interface Module (DIM).
NOTE
: 24 VAC becomes polarized when connected to DIM.
3, 4 Output
24 VAC power for Pressure Sensor
5, 6 Input
0–10 VDC pressure sensor signal
7, 8 Communications
RS-485 communications between DIM and pressure sensor
9, 10 Output
0–10 VDC pressure differential signal
- See menu item
OUTPUT SIG
11, 12 Input
Non powered switch input.
- See menu item
UNOCCUPY SET
.
13, 14 Output
Low alarm relay - N.O., closes in low alarm condition.
- See menu item
LOW ALARM
15, 16 Communications
RS-485 communications; DIM to Adaptive Offset Controller (AOC)
17- 22 No Connection
No function.
23, 24 Input
Non powered switch input – N.O. contacts for Emergency input
NOTE
: Closing these contacts puts the unit into Emergency Mode. Set
points will
not
be maintained in Emergency Mode.
25, 26 Output
High alarm relay - N.O., closes in high alarm condition.
- See menu item
HIGH ALARM
AOC
1, 2 Input
0–10 VDC flow station signal - Supply air.
3, 4 Input
Non powered switch input.
- See menu item
REM SET POINT
5– 18 Input
0–10 VDC flow station signal - fume exhaust.
21–24 Input
0–10 VDC flow station signal - General exhaust.
25–28 Input
0–10 VDC flow station signal - Supply air.
29, 30 Input
1000
Ω
RTD temperature signal
31, 32 Input
0–10 VDC flow station signal - Supply air.
33,34 Input
24 VAC to power Adaptive Offset Controller (AOC).
NOTE
: 24 VAC becomes polarized when connected to AOC.
35 Ground
Earth
ground
36, 37 Output
24 VAC Power for DIM.
38, 39 Communications
RS-485 communications; AOC to building management system (Modbus or N2)
40, 41 Communications
RS-485 communications; AOC to DIM
42, 43 Communications
LonWorks communications to building management system (optional)
BACnet MSTP communications to building management system (8682-BAC)
44, 45 Output
0–10 VDC, reheat valve control signal. 10 VDC = open (n.o. damper)
- See menu item
REHEAT SIG
46, 47 Output
0–10 VDC, supply air control signal. 10 VDC = open (n.o. damper)
- See menu item
CONTROL SIG
48, 49 Output
0–10 VDC, general exhaust control signal. 10 VDC = open (n.o. damper)
- See menu item
CONTROL SIG