Before installation, read the Safety
Warnings overleaf.
CAUTION: Risk of Danger.
Read complete
instructions prior to installation and operation of
the unit
CAUTION:
Risk of electric shock
Intended Use: The APM has been specifically designed for engineers
requiring an effective way to monitor and display data. The APM accepts a
range of electrical inputs (depending on the model) and displays the data
on its integrated multi-format display. The APM has been designed for
installation into electrical cabinets or display panels. The units come as
standard with two digital outputs and one serial output.
Operating specification
The digital readout will still show the actual voltage even if the bar
graph is out of range.
Measurement Range
Voltage / Frequency Input
0-600V DC / AC 50-60Hz
Shunt Input
0 – 500mV AC/DC
Current Input Direct
(max. 300V AC/DC)
0–5A
Frequency
(min. voltage 26V AC)
0–400Hz
DC Power Measurement
Watts
AC Power Measurement
Watts, VA, VAr
DC
0.5%
Frequency (min 20V RMS)
0.1%
AC
0.5%
Power Measurement
0.5%
Isolation
Reinforced
4KV @ 1 Sec
3KV @ 1 min
Measurement Category
CATII
Voltage / Frequency
2 MΩ
10 MΩ
Current Input Direct
4MΩ
Communication
Modbus Configured Parameters (Trumeter configurator
required): Only function code 4 – read input register
supported.
Parameter
Slave ID
0 to 255
Baud Rate
4800 to 192000
Stop Bits and Parity
2 stop bits no parity
1 stop bit even parity
1 stop bit odd parity
Communications
Enable / Disable
Modbus Registers
Address
Variable Type
Description
1-2
32bit Float
Displayed Value
(after configuration)
3-4
32bit Float
SI measured unit
(before configuration)
5
1 Byte
Alarm 1
6
1 Byte
Alarm 2
IP Address
Only adjustable if DHCP
disabled
Subnet Mask
Gateway, DNS1, DNS2, Hostname, Interface Name,
Modbus Port Address, Modbus Timeout Period.
Measurement Accuracy
Impedance
TCP/IP Parameters
Shunt
www.
GlobalTestSupply
.com