background image

 

SELF CONTAINED LED EMERGENCY 
Model: EYE-3W 

 

Self  contained  LED  1.5W  emergency  with  non-maintained  function.  Designed  in  small  size  and  round 
shape  (Ø37mm)  for  recessed  mounting.  Great  ease  of  installation.  It  incorporates  the  LiFePO4  battery 
inside the box, which achieves a very compact size. It has a green LED signaling integrated in the lamp.  

 

Characteristics: 

- Supply 230V~ 50/60Hz. 
- Input current: 25.4mA (consumption 2.9W). 
- Non maintained. 
- Green LED signaling. 
- Round LED lamp Ø37mm, white polycarbonate with false ceiling fixing spring. 
- White 1.5W SMD LED SMD of LG, high luminosity. 
- LED Working voltage: 3V 
- Battery LiFePO4 3.2V-1500mAh (located inside the equipment). 
- Autonomy: 1h or 3h depending on the model. 
- Jumper for battery disconnection. 
- Charging current: 0-200mA (floating). 
- Battery charging 24 hours. 
- Protection against overloading and end of battery discharge. 
- Grade IP20. 
- Class II device. 
- Ambient temperature: 0°C ~ 55°C 
- Recessed mounting. 
- Weight: 120gr.  
- Manufactured in according to standards: UNE-EN 60598-2-22/ UNE-EN 61347-2-7/ UNE-EN 61347-2-13  

 

MODEL 

TYPE OF LENS 

Lumens 

Autonomy 

LED current 

EYE-3W-O 

Lens for open area 

150Lm 

3 h 

400mA 

EYE-3W-C 

Lens for corridor area (evacuation route) 

150Lm 

3 h 

400mA 

EYE-3W-O2 

Lens for open area 

200Lm 

1 h 

500mA 

EYE-3W-C2 

Lens for corridor area (evacuation route) 

200Lm 

1 h 

500mA 

 

Working: 

Power presence

: The device charges permanently the battery and the two coloured LED of signaling is in 

green colour. The White LED of the equipment remains off. 

 

Power failure

: In case of power failure or low voltage, the luminary enters in emergency mode. The Green 

LED signaling goes off and the White LED of the device lights up and starts feeding from the battery. 

 

Installation: 

1.- Remove the mains voltage from the 230V installation. Always work without mains voltage. 
2.- Make a hole in the ceiling Ø32mm. 
3.- Connect the installation network cable to terminals L, N (230VAC) of the equipment. 
4.- Insert the jumper to connect the internal battery of the equipment. With the jumper removed the battery 
is disconnected. 
5.- Insert the equipment first through the hole in the false ceiling and then the lamp that is attached to the 
springs it has incorporated. 
6.- Give mains voltage to the installation and verify that the green signaling LED turns on. The device will 
not have full autonomy until 24 hours of charging. 

  

Maintenance:

 

The manipulation and the installation of the device should be done by qualified technicians. Always verify 
that the voltage of the mains is adequate to the input voltage of the device. Before installation make sure 
the mains is off. The battery LiFePO4 must be replaced when the equipment’s autonomy time is les than 1 
hour or 3 hours, depending on the model. It is convenient to write down the date of the change. 
The old battery should be recycled in a proper way, as it can be harmful for the environment. 
 

 

Dimensions: 

 
 
 
 
 

 
 
 
 
 
 
 
 
 

IP20

 

Lighting Technologies TRQ, S. L. U.

                                                               

 

 

Reviews: