2
Technical data
2.1 General data
Nominal sizes
100 – 315 mm
Casing length L
400 mm
Volume flow rate range
Up to 770 l/s or 2770 m³/h
Differential pressure range
Up to 1500 Pa
Temperature range
1, 3, 4
-20 °C to 50 °C
Release temperature
72 °C or 95 °C (for warm air ventilation systems)
Upstream velocity
2, 3
≤
8 m/s with fusible link,
≤
10 m/s with spring return actuator
Closed blade air leakage
EN 1751, Class 3
Casing air leakage
EN 1751, Class C
EC conformity
Construction Products Regulation (EU) No. 305/2011
EN 15650 – Ventilation for buildings – Fire dampers
EN 13501-3 – Classification: Fire resistant ducts and fire
dampers
EN 1366-2 – Fire resistance tests for installations: Fire
dampers
5
EN 1751 Ventilation for buildings – Air terminal devices
2006/42/EG - Machinery Directive
Declaration of performance
DoP / FKRS-EU / DE / 004
1)
Temperatures may differ for units with attachments. Details for
other applications are available on request.
2)
Data applies to uniform upstream and downstream conditions
for the fire dampers.
3)
For explosion-proof constructions of the FK-EU see the corre-
sponding operating manual.
4)
Condensation and the intake of humid fresh air have to be avoided as
otherwise operation will be impaired or not possible.
5)
Leakage rate of the fire damper system tested at 300 Pa and 500 Pa
negative pressure.