5.7.3 Installation remote from solid wood walls with mineral wool
Fig. 92: Mortar-based installation remote from a solid wood wall or CLT wall
1
FKRS-EU
2.1
Mortar
3.11
Solid wood wall / CLT wall
6.29
Mineral wool Paroc Hvac Fire Mat 80BLC
(80 kg/m³)
6.30
Reinforcing board mineral wool
Paroc Hvac Fire Mat 80BLC (80 kg/m³), glued all
round
9.2
Sheet steel duct
Up to EI 60 S
Fig. 93: Dry mortarless installation remote from a solid wood wall or CLT wall, with a fire batt
1
FKRS-EU
3.11
Solid wood wall / CLT wall
6.7
Fire batt
6.29
Mineral wool Paroc Hvac Fire Mat 80BLC
(80 kg/m³)
6.30
Reinforcing board mineral wool
Paroc Hvac Fire Mat 80BLC (80 kg/m³), glued all
round
7.11
Trim panels, single-layer, fire-resistant
8.21
Acrylic or sealing compound (suitable for fire batt
system)
9.2
Sheet steel duct
Up to EI 60 S
Additional requirements: installation remote from solid wood walls with mineral wool
Solid wood wall or CLT wall
Installation
Solid wood walls > Installation remote from solid wood walls with...
Fire damper Type FKRS-EU
110
Summary of Contents for FKRS-EU
Page 176: ...Fire damper Type FKRS EU 176...