Safety and correct use

General information regarding safety

Only specialist personnel are allowed to perform the

described work on the fire damper. Only skilled qualified

electricians are allowed to work on the electrical system.

The installation location must be easily accessible and

have sufficient clearance for electrical connection and

maintenance of the fire damper.

Standards and guidelines

Construction Products Regulation (EU) No.

305/2011

EN 15650 – Ventilation for buildings – Fire dampers

EN 13501-3 – Classification: Fire resistant ducts

and fire dampers

EN 1366-2 – Fire resistance tests for installations:

Fire dampers

EN 1751 Ventilation for buildings – Air terminal

devices

The basic safety and health requirements stipulated in

Directive 2014/34/EC are fulfilled through conformity

with the following standards:

EN 1127-1 – Explosive atmospheres – Explosion

protection: Basic concepts and methodology

DIN EN ISO 80079-36 – Explosive atmospheres:

Non-electrical equipment for explosive atmospheres

– Basic method and requirements

DIN EN ISO 80079-37 – Explosive atmospheres:

Non-electrical equipment for explosive atmospheres

- Non-electrical type of protection constructional

safety "c"

Maintenance and replacement parts

The FKRS-EU fire damper is a safety related product

that has been specially developed for fire protection. To

maintain the function, use only original TROX replace-

ment parts.

Environmental protection

To protect the environment keep the following in mind:

Dispose of packaging in an environmentally sound

manner.

Have used fire damper components or the used fire

damper only disposed of by an authorised company.

Dispose of electronic components according to the

local electronic waste regulations.

Correct use

The fire damper is used as a shut-off device to prevent

fire and smoke from spreading through ducting in areas

with potentially explosive atmospheres.

The fire damper may be used in supply air or extract air

systems in areas with potentially explosive atmos-

pheres.

For details on the operation of the fire dampers, refer to

the operating and installation manual FKRS-EU and the

technical data in this supplementary operating manual.

Use in areas with potentially explosive atmospheres

(ATEX)

In accordance with the certificate of conformity

EPS 21 ATEX 2 142 X, the fire damper can be used in

certain Ex zones. The ambient temperatures and types

of release and actuation specified in the technical data

are binding, .

Incorrect use

The following applications are not allowed:

For use

as a smoke control damper,

as an air transfer damper,

outdoors without sufficient protection against the

effects of weather,

in extract air systems in commercial kitchens,

in ventilation systems in which high levels of dust

and pollution, extreme humidity, or chemical con-

tamination may impair the function of the unit and

in installation situations that prevent an inspection of

the internal components of the fire damper.

Modifying the fire damper or using replacement parts

that have not been approved by TROX is not permitted.

Residual risks

TROX fire dampers are subject to strict quality controls

during manufacturing. In addition, a functional test is

performed before shipping.

Damage can, however, occur during transport or instal-

lation and impair the function of the fire damper.

In any case, the proper function of the fire damper must

be checked during commissioning, and ensured through

regular maintenance while in use.

Safety and correct use

 

 

Explosion-proof fire damper Type FKRS-EU

5

Summary of Contents for FKRS-EU Series

Page 1: ...Explosion proof fire damper Type FKRS EU Supplementary Operating Manual Read the instructions prior to performing any task according to Declaration of Performance DoP FKRS EU DE 004 GB en...

Page 2: ...original 2021 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Germany Phone 49 0 2845 2020 Fax 49 0 2845 202 265 E mail trox de troxgroup de Internet http www troxtechnik com 12 2021 Exp...

Page 3: ...data 6 3 1 FKRS EU with explosion proof spring return actuator 6 3 2 ATEX areas of application 7 4 Electrical connection 8 5 Functional test 10 5 1 FKRS EU with ExMax or RedMax spring return actuator...

Page 4: ...nt statutory regulations This supplementary operating manual is intended for specialist consultants developers and owners of the ventilation systems in which the fire dampers are to be installed This...

Page 5: ...components according to the local electronic waste regulations Correct use The fire damper is used as a shut off device to prevent fire and smoke from spreading through ducting in areas with potentia...

Page 6: ...ght kg Nominal size DN 100 125 150 160 180 200 224 250 280 315 D 99 124 149 159 179 199 223 249 279 314 Weight with spring return actuator 4 8 5 1 5 3 5 5 5 8 6 0 6 2 6 8 7 3 7 9 Spring return actuato...

Page 7: ...ExMax 15 BF TR II 2G Ex h IIC T6 Gb II 2D Ex h IIIC T80 C Db 40 C Ta 40 C 10 m s ExPro TT ExMax 15 BF TR II 2G Ex h IIC T5 Gb II 2D Ex h IIIC T95 C Db 40 C Ta 50 C 10 m s ExPro TT RedMax 15 BF TR II...

Page 8: ...on Functional testing requires a switch that interrupts the voltage supply by others The electrical connection is made in the terminal box The factory installed wiring must not be changed Attention If...

Page 9: ...Wiring example for TROXNETCOM Fig 3 Wiring example for TROXNETCOM 1 Controller 2 AS EM C module 3 FKRS EU 4 Safe area Electrical connection Explosion proof fire damper Type FKRS EU 9...

Page 10: ...2 Damper blade is open Closing opening the fire damper with spring return actuator Fig 5 Thermoelectric release mechanism ExPro TT 1 Push button for functional test Fig 6 Functional test FKRS EU with...

Page 11: ...de will not close To re establish its function connect the power supply Requirement The damper blade is CLOSED 1 Remove the terminal box 1 2 Insert the crank handle 2 into the opening for the spring w...

Page 12: ...Explosion proof fire damper Type FKRS EU 12...

Reviews:

Related manuals for FKRS-EU Series