Table of the fan rating groups
According to ISO 14694 (2003), Chapter 8.4
Application
Max. drive capacity [kW]
Fan rating group
Building ventilation
≤ 3.7
BV-2
> 3.7
BV-3
Hazardous gases
≤ 37
BV-3
> 37
BV-4
Table of impeller gaps for axial fans
Size
Impeller gap (+ tolerance) in mm
AXN;
BVAXN
F200
AXO;
BVAXO
F200/F300
BVAXN
F300
BVAXN
F400
BVAXN
F600
AXN-ex
AXO-ex
250
1.0 (+1.0)
1.0 (+1.0)
2.0 (+1.0)
280
1.0 (+1.0)
1.0 (+1.0)
2.0 (+1.0)
315
1.0 (+1.0)
1.0 (+1.0)
1.0 (+1.0)
2.4 (+1.0)
2.0 (+1.0)
2.0 (+1.0)
355
1.5 (+1.3)
1.5 (+1.3)
1.5 (+1.3)
2.5 (+1.3)
2.5 (+1.5)
400
1.5 (+1.3)
1.5 (+1.3)
1.5 (+1.3)
2.9 (+1.3)
2.0 (+1.3)
3.0 (+1.5)
3.0 (+1.5)
450
2.0 (+1.5)
2.0 (+1.5)
2.0 (+1.5)
2.0 (+1.5)
2.0 (+1.5)
3.0 (+1.5)
500
2.0 (+1.5)
2.0 (+1.5)
1.5 (+1.5)
2.9 (+1.5)
3.0 (+1.5)
4.0 (+1.5)
4.0 (+1.5)
560
2.0 (+1.5)
2.0 (+1.5)
2.0 (+1.5)
3.1 (+1.5)
3.0 (+1.5)
630
2.5 (+1.5)
2.5 (+1.5)
2.0 (+1.5)
3.3 (+1.5
3.5 (+1.5)
4.0 (+1.5)
4.0 (+1.5)
710
3.0 (+2.0)
3.0 (+2.0)
3.0 (+2.0)
3.6 (+2.0)
4.5 (+2.0)
4.5 (+2.0)
800
3.0 (+2.0)
3.0 (+2.0)
4.5 (+2.0)
4.1 (+2.0)
5.0 (+2.0)
5.0 (+2.0)
5.0 (+2.0)
900
3.5 (+2.5)
3.5 (+2.5)
3.0 (+2.5
4.6 (+2.5)
6.0 (+2.5)
5.5 (+2.5)
1000
4.0 (+2.5)
4.0 (+2.5)
4.5 (+2.5)
5.1 (+2.5)
6.5 (+2.5)
6.0 (+2.5)
6.0 (+2.5)
1120
4.5 (+3.0)
4.5 (+3.0)
3.5 (+3.0)
5.7 (+3.0)
7.0 (+3.0)
7.0 (+3.0)
1250
5.0 (+3.0)
5.0 (+3.0)
5.5 (+3.0)
6.4 (+3.0)
7.5 (+3.0)
8.5 (+3.0)
1400
5.0 (+3.0)
5.0 (+3.0)
7.5 (+3.0)
6.0 (+3.0)
8.0 (+3.0)
9.5 (+3.0)
1600
6.0 (+3.0)
6.0 (+3.0)
7.5 (+3.0)
7.0 (+3.0)
9.0 (+3.0)
10.5 (+3.0)
1800
6.5 (+4.0)
6.5 (+4.0)
11.5 (+4.0)
2000
7.5 (+4.0)
7.5 (+4.0)
13.0 (+4.0)
2240
8.0 (+4.0)
8.0 (+4.0)
14.5 (+4.0)
2500
9.0 (+4.0)
9.0 (+4.0)
16.0 (+4.0)
Tables
Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN
61