12.4 Installation location
The axial fan may need to be removed for it to be main-
tained and repaired. The following conditions must be
maintained at the installation location:
Fig. 41: Space requirements of the axial fan
In the case of plenum installation, clearance of the
following size to the side of the axial fan: (1) fan
nominal size x 0.5 (2) fan nominal size + 1 m
The axial fan must be accessible without hindrance
at all times.
Sufficient space of this size must be provided in the
case of roof assembly.
Space for a mounting frame must be kept free
above and around the axial fan.
Fig. 42: Minimum distance
The minimum distance between the axial fan and
the walls and neighbouring axial fans must be at
least 0.5 x the fan size.
Installation and assembly recommendations f...
Installation location
Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN
51