Fig. 3: Installation
COMMISSIONING
The air flow rate is adjusted by turning the centre cone. It is fixed in
place by tightening the lock nut at the rear of the centre bolt. Valve
commissioning is carried out by measuring the pressure difference at
the back of the centre cone, and calculating the air flow rate according
to correction factor for valve dimension and centre cone position. Cor-
rection factors are provided on a label attached to the valve and
can also be found in our commissioning guide available at our website:
www.trox.no.
MAINTENANCE
The valve can be cleaned by using a damp cloth. When cleaning the
duct network, the valve must be removed in order to gain access to
the ducting.
ENVIRONMENT
Enquiries regarding product declaration can be directed to our sales
team, or information can be found at www.trox.no.
INSTALLATION
Separate mounting frame (DKT) is attached to the duct by using
blind rivets or self-drilling screws. The valve is then screwed into the
mounting frame. Installation principle is shown in fig. 3.