background image

EN

3

dehumidifier TTK 175 S / TTK 355 S

Safety

Read this manual carefully before starting or using the
device. Always store the manual in the immediate vicinity
of the device or its site of use.

Warning
Read all safety warnings and all instructions.

Failure to follow the warnings and instructions may
result in electric shock, fire and/or serious injury.

Save all warnings and instructions for future
reference.

In the scope of European normative requirements 
(EN 60335-1):
This appliance can be used by children aged from 8 years
and above and persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge if
they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the
hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall not be
made by children without supervision.

In the scope of International normative requirements 
(IEC 60335-1):
This appliance is not intended for use by persons
(including children) with reduced physical sensory or
mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning use of the appliance by a person responsible
for their safety. Children should be supervised to ensure
that they do not play with the appliance.

Do not use the device in potentially explosive rooms or
areas and do not install it there.

Do not use the device in aggressive atmosphere.

Only put up the device in an upright, stable position on firm
ground.

Let the device dry out after a wet clean. Do not operate it
when wet.

Do not use the device with wet or damp hands.

Do not expose the device to directly squirting water.

Do not cover the device during operation.

Do not sit on the device.

This appliance is not a toy. Keep away from children and
animals.

Occasionally observe the device during operation.

Check accessories and connection parts for possible
damage prior to every use of the device. Do not use any
defective devices or device parts.

Ensure that all electric cables outside of the device are
protected from damage (e.g. caused by animals). Never
use the device if electric cables or the power connection
are damaged!

The mains connection must correspond to the
specifications in the Technical annex.

Insert the mains plug into a properly fused mains socket.

Observe the device's power input, cable length and
intended use when selecting extensions to the power
cable. Completely unroll extension cables. Avoid electrical
overload.

Do not under any circumstances use the device if you
detect damages on the mains plug or power cable. 
If the power cable is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Defective power cables pose a serious health risk!

Before carrying out maintenance, care or repair work on
the device, remove the mains plug from the mains socket.
Hold onto the mains plug while doing so.

Switch the device off and disconnect the power cable from
the mains socket when the device is not in use.

When positioning the device, observe the minimum
distances from walls and other objects as well as the
storage and operating conditions specified in the Technical
annex.

Make sure that the air inlet and outlet are not obstructed.

Make sure that the suction side is kept free of dirt and
loose objects.

Never insert any objects or limbs into the device.

Do not remove any safety signs, stickers or labels from the
device. Keep all safety signs, stickers and labels in legible
condition.

Only transport the device in an upright position with an
emptied condensation tank or drain hose.

Discharge the collected condensate before transport and
storage. Do not drink it. Health hazard!

Only use original spare parts, for otherwise safe and
functional operation cannot be ensured.

Safety warnings for devices containing flammable
refrigerants

Only position the device in rooms where potentially leaking
refrigerant cannot accumulate. Unventilated rooms, in
which the device is installed, operated or stored, must be
built in a way to ensure that potentially leaking refrigerant
cannot accumulate. This serves to avoid fire or explosion
hazards resulting from an ignition of the refrigerant by an
electric furnace, cooking stove or another ignition source.

Summary of Contents for TTK 175 S

Page 1: ...TRT BA TTK175S TTK355S TC220617TTRT01 011 EN TTK 175 S TTK 355 S EN ORIGINAL INSTRUCTIONS DEHUMIDIFIER...

Page 2: ...indicates dangers to the life and health of persons due to electrical voltage Warning This signal word indicates a hazard with an average risk level which if not avoided can result in serious injury...

Page 3: ...bles outside of the device are protected from damage e g caused by animals Never use the device if electric cables or the power connection are damaged The mains connection must correspond to the speci...

Page 4: ...work require the support of additional persons the person trained in handling flammable refrigerants shall continuously supervise the work carried out The entire refrigerant circuit is a maintenance f...

Page 5: ...ger Refrigerant R454C H220 Extremely flammable gas H280 Contains gas under pressure may explode if heated P210 Keep away from heat sparks open flames and other ignition sources No smoking P381 Elimina...

Page 6: ...dehumidify rooms The fan sucks damp room air through the air inlet the air filter the evaporator and to the condenser located behind it The air is cooled at the cold evaporator until it is below the...

Page 7: ...the remaining condensate from the device and the condensation drain hose see chapter Maintenance Do not use the power cable to drag the device Only wheel the device on firm and level surfaces Please n...

Page 8: ...llowing storage conditions Only store the device in a room measuring more than 4 m2 Only position the device in rooms where there is no source of ignition e g open flames an active gas appliance or an...

Page 9: ...ke sure that no curtains or other objects interfere with the air flow When positioning the device particularly in wet areas secure it locally with an RCD residual current device which complies with th...

Page 10: ...10 EN dehumidifier TTK 175 S TTK 355 S 1 2 3 4 5...

Page 11: ...f energy consumption 14 Rotary switch Selection of relative room humidity 15 Mains switch Switching the device on and off Is illuminated when the device is switched on 16 Condensation tank LED Is disp...

Page 12: ...is only functional after three to five minutes each time it is switched on or after the water container has been inserted 1 Ensure that the condensation drain hose is properly connected to the device...

Page 13: ...tect e g the compressor from overheating Upper temperature limit 35 C 2 C Lower temperature limit 3 C 2 C If the ambient temperature exceeds or falls below these limits the device automatically switch...

Page 14: ...the power cable and mains plug for damage Check the on site fusing Check the filling level of the condensation tank and empty it if necessary The Condensation tank LED 16 must not light up Check the c...

Page 15: ...y a specialist company for cooling and air conditioning or by Trotec Note Wait for at least 3 minutes after maintenance and repair work Only then switch the device back on The device still does not op...

Page 16: ...ank and or drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign object...

Page 17: ...if heated P210 Keep away from heat sparks open flames and other ignition sources No smoking P381 Eliminate all ignition sources if safe to do so P403 Store in a well ventilated place The entire refrig...

Page 18: ...ith a neutral cleaning agent 3 Allow the filter to dry completely Do not insert a wet filter into the device 4 Reinsert the air filter into the device Emptying the condensation tank Info The compresso...

Page 19: ...tion tank LED 16 will be illuminated The compressor and fan will switch off Activities required after maintenance If you want to continue using the device Reconnect the device to the mains If you do n...

Page 20: ...Pa Air volume flow 580 m h 580 m h 1 000 m h Mains connection 220 240 V 50 Hz 110 230 V 50 Hz 220 240 V 50 Hz Power consumption max 0 6 kW 0 6 kW 1 3 kW Nominal current 2 8 A 5 7 2 7 A 6 A Fusing 10 A...

Page 21: ...EN 21 dehumidifier TTK 175 S TTK 355 S Wiring diagram With operating hours counter...

Page 22: ...22 EN dehumidifier TTK 175 S TTK 355 S With operating hours counter and MID counter...

Page 23: ...N 23 dehumidifier TTK 175 S TTK 355 S Exploded assembly drawing Info The position numbers of the spare parts differ from those describing the positions of the components mentioned in these instruction...

Page 24: ...rity pin 7 Left panel 24 Electronic controller 41 Rubber feet 8 Water tank baseplate complete set 25 Main switch 42 Control panel sticker 9 Structural foot 26 Electronic controller status LED 43 Axle...

Page 25: ...ur country The separate collection of waste electrical and electronic equipment aims to enable the re use recycling and other forms of recovery of waste equipment as well as to prevent negative effect...

Page 26: ...0 2003 A2 2009 EN 60335 2 40 2003 A11 2004 EN 60335 2 40 2003 A12 2005 EN 60335 2 40 2003 A13 2012 EN 60335 2 40 2003 AC 2006 EN 60335 2 40 2003 AC 2010 EN 60335 2 40 2003 AC 2013 EN 61000 3 3 2013 Ap...

Page 27: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: