Pre-Installation Instructions
8014 Trotec Speedy 500
Water Chiller Requirements
13/12/2011
Trotec Produktions- und Vertriebs GmbH
_Linzer Strasse 156, A-4600 Wels, Austria, Technical Support
14 / 15
tel_+43 (0)7242 239-7000, fax_+43 (0)7242 239-7380, mailto:
4 Water Chiller Requirements
For machines fitted with water-cooled laser tubes, you need a water cooling unit.
4.1 Cooling Requirements for laser tubes
Laser power [W]:
60
120
200
Minimum cooling capacity [W]
500
2300
4000
Minimum flow rate [l/min]
at 18 to 22°C
6 10
11,4
Maximum pressure [bar]
4,2
4,2
4,2
Pressure loss [bar]
1,2
-
1,4
4.2 Electrical Requirements and other specifications for Trotec chillers
EU US
Laser power [W]
60 120 200 60 120 200
Voltage [V]
1x230
1x230 1x230 1x115 1x115V 1x230
Frequency [Hz]
50/60
50/60
50
60
60
50/60
Phases
L, N,
Ground
L, N,
Ground
L, N,
Ground
L, N,
Ground
L, N,
Ground
L, N,
Ground
Power consumption [W]
900 W
1800 W
3000
900
1800
3000
4.3 General notes regarding Trotec chillers
All chillers are delivered with Europe C19 plugs.
The coolant temperature has to be between 18 and 25°C.
If temperature falls below this range, the chiller might not be ready for operation and the coolant has
to be warmed.
4.4 Water Requirements for chiller and laser tube
Please, use normal tap water as coolant. The use of de-ionized, de-mineralized or distilled water is
not recommended and can destroy the laser tube.
Ideal water quality
Ph-value: 7-9
Alkalinity (°dH): <1
Conductivity: <300
μ
S/cm
Chloride content: <20 mg/L
Hardness (°dH): <0,1
Organic germs: <1000 KBE/ml
In case of deviations of water quality, it is recommended to us softening agents, corrosion inhibitors
or biocide additives.