Operating manual – local air conditioner PAC 2000 S / PAC 2600 S

Errors and faults

The device has been checked for proper functioning several
times during production. If malfunctions occur nonetheless,
check the device according to the following list.

The device does not start:

Check the power connection.

Check the power cable and mains plug for damages.

Check the on-site fusing.

Observe the operating temperature according to the
Technical data chapter.

The condensation tank may be full. Empty the
condensation tank, if need be. The error code 

E4

 must not

be indicated on the segment display.

Wait for 10 minutes before restarting the device. If the
device is not starting, have the electrics checked by a
specialist company or by Trotec.

The device works with reduced or no cooling capacity:

Check whether 

cooling

 mode is selected.

Check the proper fit of the exhaust air hose. In case of
kinks, bends or blockage in the hose, exhaust air cannot
be discharged. Clear the way for the exhaust air.

Check the position of the ventilation flaps. They should be
opened to the maximum.

Check the air filter(s) for dirt. If necessary, clean or replace
the air filter(s).

Check the minimum distance to walls or other objects.
Position the device a little more in the room's centre if
required.

Check whether any windows and/or doors of the room are
open. If so, close them. The window for the exhaust air
hose has to remain open nonetheless.

Check the temperature setting at the device. Reduce the
set temperature if it is higher than the room temperature.

The device is loud or vibrates:

Check whether the device is set up in a stable and upright
position.

Condensate is leaking:

Check the device for leaks.

The compressor does not start:

Check whether the overheating protection of the
compressor has tripped. Disconnect the device from the
mains and let it cool down for approx. 10 minutes before
reconnecting it.

Check whether the ambient temperature equals the target
temperature (in 

cooling

 mode). The compressor will not

switch on unless the respective temperature is reached.

The compressor may start up with a delay of 3 min, as it is
provided with an internal protection against direct restart.

The device gets very warm, is loud or loses power:

Check the air inlets and air filters for dirt. Remove external
dirt.

From the outside, check the device for dirt (see chapter
Maintenance). If the inside of the device is dirty, have it
cleaned by a specialist company for cooling and air-
conditioning or by Trotec.

The device does not respond to the infrared remote control:

Check whether the distance between remote control and
device is too large and reduce it if necessary.

Make sure there are no obstacles, such as furniture or
walls, between the device and the remote control. Ensure
visual contact between device and remote control.

Check the charging status of the batteries and change
them if required.

If the batteries have only just been changed, check them
for correct polarity and change them if required.

Note

Wait for at least 3 minutes after maintenance and
repair work. Only then switch the device back on.

Your device still does not operate correctly after these
checks?

Please contact the customer service. If necessary, bring the
device to a specialist company for cooling and air-conditioning
or to Trotec for repair.

Error codes

The following error messages can be displayed on the segment
display (15):

Error
code

Cause

Remedy

E2

Error at the room
temperature
sensor

Disconnect the device briefly
from the mains.
Should the error still be
displayed after the restart,
please contact the customer
service.

E3

Error at the
temperature
sensor of the
evaporator

E5

Error at the
temperature
sensor of the
condenser

E4

Condensation
tank full

Empty the condensation tank
(see chapter Maintenance,
Condensate discharge (manual
draining)). Should the error still
be displayed, please contact the
customer service.

Summary of Contents for PAC 2000 S

Page 1: ...TRT BA PAC2000S PAC2600S TC 001 EN PAC 2000 S PAC 2600 S EN OPERATING MANUAL LOCAL AIR CONDITIONER...

Page 2: ...lowing link PAC 2000 S http hub trotec com id 42257 PAC 2600 S http hub trotec com id 42258 Safety Read this manual carefully before starting or using the device Always store the manual in the immedia...

Page 3: ...When positioning the device observe the minimum distances from walls and other objects as well as the storage and operating conditions specified in the Technical data chapter Ensure that the air inle...

Page 4: ...Hold onto the mains plug while pulling the power cable out of the mains socket 3 Do not reconnect a defective device to the mains Information about the device Device description The device serves the...

Page 5: ...evice Transport To make the device easier to transport it is fitted with wheels Before transporting the device observe the following Switch the device off Hold onto the mains plug while pulling the po...

Page 6: ...the device 1 Open the cardboard box and take the device out 2 Completely remove the packaging 3 Fully unwind the power cable Make sure that the power cable is not damaged and that you do not damage i...

Page 7: ...reduce the dehumidification performance and result in damage to the device Make sure that the air filter is installed before switching the device on 900 Connecting the exhaust air hose 1 Connect the...

Page 8: ...not shift The end of the exhaust air hose can also be hooked into a tilted window For this purpose we recommend using a window seal optional Install the exhaust air hose inclined with the air directio...

Page 9: ...LED Illuminated when the timer is activated 18 Operating light Indicates operation Device is switched on or off 19 Power button Switching the device on and off 20 Night mode LED Illuminated when night...

Page 10: ...ntil the cooling LED 24 is illuminated The current room temperature is indicated on the segment display 15 2 Repeatedly press the plus 14 or minus 22 button to select the desired target temperature Th...

Page 11: ...ion 5 3 Connect the condensation drain hose to the hose connection 5 4 Guide the other hose end to a suitable drain or sufficiently dimensioned collection container To ensure that the condensate can r...

Page 12: ...ber of hours until automatic switch off will be indicated on the segment display 15 for approx 3 s The timer LED 17 is illuminated Then the segment display 15 changes back to the current room temperat...

Page 13: ...the timer 1 h to 24 h 23 Operating mode button Selecting the operating mode ventilation dehumidification cooling automatic operation Automatic defrost At low ambient temperatures ice may form at the e...

Page 14: ...down for approx 10 minutes before reconnecting it Check whether the ambient temperature equals the target temperature in cooling mode The compressor will not switch on unless the respective temperatur...

Page 15: ...t every 6 months at least annually Check air inlets and outlets for dirt and foreign objects and clean if necessary X X Clean the exterior X X Visually check the inside of the device for dirt X X Chec...

Page 16: ...of the device for dirt Check the air filter for dirt and foreign objects and clean or replace if necessary Replace the air filter Check for damage Check the attachment screws Test run Remarks Empty th...

Page 17: ...3 Check the inside of the device for dirt 4 If you see a thick layer of dust have the inside of the device cleaned by a specialist company for cooling and air conditioning or by Trotec 5 Put the air f...

Page 18: ...ught to be drained regularly 1 Carefully transport or wheel the device to a suitable location for discharging the condensate e g a drain or position a suitable collection container under the condensat...

Page 19: ...hours so the refrigerant can accumulate within the compressor Wait 12 to 24 hours before switching the device back on Acting contrary might lead to compressor damage and a malfunctioning device If so...

Page 20: ...find collection points for free return of waste electrical and electronic equipment in your vicinity The addresses can be obtained from your municipality or local administration For further return op...

Page 21: ......

Page 22: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: