background image

 

User Manual Qiwi Lite 
Support: www.tronteq.de/support 
Release 11/2016 

 

Seite 29 von 31

 

12.  Technical data 

12.1.  Electrical 

 
Power Ports 

Parameter  

min. 

typ. 

max. 

Dim. 

Operating voltage (V1, V2) SELV 

Direct current voltage  

Small alternating voltage  

 

9,6 

18 

 

24 

24 

 

60 

32 

 

V dc 

V ac 

Reset level (V1, V2) 

9,0 

V dc 

Current consumption, full load all ports 

V1,V2 = 9.6V 
V1,V2 = 24V 
V1,V2 = 60V 

 



 

250 
100 

65 

 



 

mA 
mA 
mA 

Peak inrush current 

<1ms 

 

 

10 @ 9,6V 

 

14 @ 60V 

 

Power consumption 

V1,V2 = 9.6V 
V1,V2 = 24V 
V1,V2 = 60V 

 



 

2.40 
2.40 
3.90 

 

2.65 
2.65 
4.20 

 



Bridging of power outage 

10 

ms 

Operating voltage (V1, V2) SELV 

Direct current voltage  

Small alternating voltage  

 

9,6 

18 

 

24 

24 

 

60 

32 

 

V dc 

V ac 

 

Ethernet Ports 

Parameter  

min. 

typ. 

max. 

Dim. 

Switch architecture 

Store-and-Forward 

Bitrate 

10/100 

Mbit/s 

Output resistance 

100 

 

Input resistance 

100 

 

Latency (Packet size 64Byte 

– 1518Byte) 

at 100Mbit/s 
at 10Mbit/s 

 


 

8.0 
8.0 

 


 

µs 
µs 

Throughput Unicast- Packet 

Packet size 64Byte 

– 1518Byte 

Full wire 

speed 

pps 

Throughput Multicast- Packet 

Packet size 64Byte 

– 1518Byte 

Full wire 

speed 

pps 

Packet size 

without VLAN Tag 
with VLAN Tag 

 

64 
64 

 


 

1518 
1522 

 

Byte 
Byte 

 
 

 

Summary of Contents for Qiwi Lite

Page 1: ...User Manual Qiwi Lite Support www tronteq de support Release 11 2016 Seite 1 von 31 User Manual Industrial Ethernet Switch Lite Managed Qiwi Lite Order No 006 120 101 ...

Page 2: ...s allowed as part of use of TRONTEQ products Any other use which goes beyond in particular copying reproduction translation requires written consent of TRONTEQ Electronic TRONTEQ Electronic reserves the right to modify the contents of this manual In addition we refer to the conditions of use specified in the license agreement The latest version of this manual is available online at www tronteq de ...

Page 3: ...0 4 2 First operation 10 5 Configuration with web interface 11 6 Settings of the system 13 6 1 Ethernet Ports 13 6 2 Port Mirroring 14 6 3 Link Aggregation 15 6 4 VLAN 16 7 Device Diagnosis 18 7 1 LED display 18 7 2 Status codes 18 7 3 Fault contact 19 7 4 TRAP 20 7 5 Diagnosis services 21 7 5 1 SNMP 21 7 5 2 Modbus TCP 21 7 6 Digital Input 23 7 7 Logging 23 8 Configuration system access 24 8 1 IP...

Page 4: ...User Manual Qiwi Lite Support www tronteq de support Release 11 2016 Seite 4 von 31 ...

Page 5: ...s instruction are provided for basic understanding and may differ from the actual design 1 2 Warning information system This manual contains notices you have to observe in order to ensure your personal safety as well as to prevent damage to property The notices referring to your personal safety are highlighted in the manual by a safety alert symbol notices referring only to property damage have no...

Page 6: ...ation All information and instructions in this operating instruction has been compiled in accordance with current standards and regulations state of the art as well as the knowledge and experience of the applications in the field In the following cases the manufacturer is not liable for damages Disregard of the operating instructions in this manual Improper use Employment of non qualified personne...

Page 7: ...th a very good price performance ratio Further the Qiwi Lite supports basic configurations such as VLANs Quality of Service Port Shutdown Fault Contact and Digital Input 2 2 Product Features Feature Description Enclosure IP20 DIN rail Power supply 9 60 VDC redundant 2x Vin Hardware Store and Forward Architecture Auto Negotiation Auto MDI MDI X Fault contact 2A 60V Digital Input 24V EN 60131 LEDs P...

Page 8: ...wiring electrical connections if they are under voltage Do not perform any assembly work on the device when it is under voltage 3 1 Mounting Perform the following steps for mounting the device Make sure that all electrical connectors are volt free Make sure that the device is disconnected from all connections Mount the device on a DIN rail Mount the device on a flat surface with four M4 screws Gro...

Page 9: ...wer supply 1 and 2 minus pole 8 V2 Power supply 2 plus pole 3 3 Connecting the Fault Contact See chapter 3 2 3 4 Connecting the Digital Input See chapter 3 2 3 5 Connecting the USB flash drive The connection is performed with the USB A port of the device Pin Assignment Connection Image 1 VBUS 5V 2 D Data 3 D Data 4 GND Ground not connected with shielding 3 6 Connecting the Ethernet ports The conne...

Page 10: ...ort Mirroring deactivated Link Aggregation deactivated Fault Contact Normally Open Fault Contact Events V1 or V2 fault over temperature TRAP protocol UDP TRAP IP address 192 168 0 1 4321 TRAP events V1 or V2 fault over temperature internal fault Logging function activated 4 2 First operation Proceed as follows for the first operation 1 Connect the power supply 2 Connect the PC notebook to one of t...

Page 11: ...tch must be typed in the web interface to get access The default IP address is 192 168 0 2 To get access to the system the user must authenticate This will be done using a user name and a password Subsequently the web interface will be loaded The default access is configured as follows User admin Password password If in the network Broadcast packets are sent permanently through the Switch the web ...

Page 12: ...onfigurations or uploads firmware updates The current page is highlighted in color The status bar at the top of the Web page shows the most important information of the system and updates it every 10 seconds There you can find the state of the devices LEDs the state of power supply the state of the fault contact the last error the temperature and the amount of time the system already is active Aft...

Page 13: ...emicolon no new line Description description of the interface max 64 characters no semicolon no new line Link enable port activated disable port deactivated Speed 100 MBit port set to 100 MBit 10 Mbit port set to 10 MBit auto port uses auto negotiation Duplex full port uses full duplex half port uses half full duplex auto port uses auto negotiation QoS Port All incoming packets of the configured p...

Page 14: ...ort With QoS Quality of Service the data traffic is prioritized in a network The switch supports two different procedures Ports based QoS can be activated on maximum 4 ports For the frame based QoS there is no such limitless 6 2 Port Mirroring Port mirroring or port monitoring makes it possible to duplicate network traffic to an observation port and to analyze it there Per port the incoming and ou...

Page 15: ...ple ports to enable a higher and redundant data throughput between two devices The setting to Link Aggregation You can find in the web interface at Configuration Link Aggregation Each interface can be assigned to Group A or Group B To confirm the settings click on the submit button Max 2 groups are supported by the device The connected devices must be configured for Link Aggregation ...

Page 16: ...re at the port in the first column are only forwarded to ports which have a check mark in the row of the respective port In most cases the switching for incoming and outgoing traffic is symmetric To activate symmetric features click on the check box symmetric To apply the chosen settings click on submit all For better and faster configuration just click on check all or clear all to select all or n...

Page 17: ...User Manual Qiwi Lite Support www tronteq de support Release 11 2016 Seite 17 von 31 If different VLANs are wired problems with data transfer occur It is recommended to configure one common VLAN ...

Page 18: ...ed configuration file was invalid red flashes with 10Hz The fault contact is active red flashes with 30Hz There is an error with the power supply red lights up Internal system fault or over temperature DI none Digital input is not active green lights up Digital input is active Ethernet port LED Each Ethernet port hast two LEDs The meaning of each LED is shown in this table LED Color Activity Opera...

Page 19: ...guration of the Fault Contact is performed in the web interface at Configuration Fault Contact Different events see chapter 7 2 can be set as trigger for the Fault Contact Power active as default Temperature active as default Linkdown Internal Digital Input Further the reset of the Fault Contact is configured in two different manners automatic The Fault Contact is automatically reset inactive if t...

Page 20: ...f the data packet consists of two bytes which contains the current fault status In the web interface the following configurations can be made at Configuration System Traps activate deactivate default activated Protocol TCP UDP default UDP Target IP address default 192 168 0 1 Target port default 4321 As trigger for Traps one or several of the following fault statuses can be configured Power active...

Page 21: ...nd can be requested with get and getnext System Group 1 3 6 1 2 1 1 Interfaces Group 1 3 6 1 2 1 2 Address Translation Group 1 3 6 1 2 1 3 IP Group 1 3 6 1 2 1 4 ICMP Group 1 3 6 1 2 1 5 TCP Group 1 3 6 1 2 1 6 UDP Group 1 3 6 1 2 1 7 SNMP Group 1 3 6 1 2 1 11 In the System Group the data is sent that is configured at Configuration System of the web interface 7 5 2 Modbus TCP With Modbus TCP the s...

Page 22: ...lt LED 0x0000 Off 0x0001 On 0x005B 0x007F Invalid range Can not be requested 0x0080 1 word Di 1 0x0000 Off 0x0001 On 0xFFFF No Di 0x0081 1 word Di 2 0x0000 Off 0x0001 On 0xFFFF No Di 0x0082 1 word Do 1 0x0000 Off 0x0001 On 0xFFFF No Do 0x0083 1 word Do 2 0x0000 Off 0x0001 On 0xFFFF No Do 0x0084 0x008F Invalid range Can not be requested 0x0090 4 word Product Serial Number 0x0095 0x009F Invalid rang...

Page 23: ... in the web interface at Configuration System under Gerneral Settings Per default the Logging is deactivated The log entries are displayed in the web interface at Monitoring Logging The following table is an example of the log entries Time Type Description 0 day s 00 00 00 device power on 0 day s 00 00 00 fault contact inactive 0 day s 00 00 00 device booted 0 day s 00 00 01 interface interface 6 ...

Page 24: ...ubmit button to confirm the settings The default settings are IP address 192 168 0 2 Subnet mask 255 255 255 0 Gateway 192 168 0 1 Changes of those settings become active after a restart of the system With the button reboot a restart of the device is performed 8 2 Administration port The access to the web interface of the device can be blocked on certain ports The configuration is performed in the...

Page 25: ...s the content is the new user name and new password The requirements of the format are described in chapter Fehler Verweisquelle konnte nicht gefunden werden For the password the following conventions must be complied at least 5 characters max 16 characters no special character no umlauts After you put in the USB flash drive the password is automatically changed without a restart If a web interfac...

Page 26: ...le must be on the USB flash drive The authentication file must be an ASCII coded test file without formatting In the first line must contain the user name the second the password The structure of the directory of the USB flash drive must look like that USB flash drive directory userpassword pass log logfile1 log logfile2 log configuser config cfg confignew cfg newpassword pass OSYS_TQPRODUCT_Rxx b...

Page 27: ...te via web interface You can find the option at Maintaining Update Firmware After selecting the start firmware update you can select the pop up window in the firmware file After that you can transfer the firmware update to your device by clicking the upload button It will start automatically 10 2 Firmware update via USB flash drive To install a firmware update via an USB flash drive an authenticat...

Page 28: ... to all supported functions of the device Navigate to the Help menu on the bottom left side of the web interface Click on a term that you want to be explained a window with short information will come up Click on Open as site and info as pop up and you will get to the web site of the actual term The help information text will appear in a pop up window ...

Page 29: ...V1 V2 9 6V V1 V2 24V V1 V2 60V 2 40 2 40 3 90 2 65 2 65 4 20 W W W Bridging of power outage 10 ms Operating voltage V1 V2 SELV Direct current voltage Small alternating voltage 9 6 18 24 24 60 32 V dc V ac Ethernet Ports Parameter min typ max Dim Switch architecture Store and Forward Bitrate 10 100 Mbit s Output resistance 100 Input resistance 100 Latency Packet size 64Byte 1518Byte at 100Mbit s at...

Page 30: ...unding 2250 VDC Fault contact V1 V2 USB housing 1500 VDC Housing grounding V1 V2 USB 850 VDC Data ports data ports 2250 VDC 12 2 Mechanical Parameter typ Dim Dimensions H x B x T 0 5 mm 64 x 105 x 48 mm Mass net 250 g Housing protection class IP20 12 3 Environment Parameter min typ max Dim Ambient temperature during operation 40 70 C Ambient temperature storage 40 85 C Humidity not condensing 10 9...

Page 31: ...ite Support www tronteq de support Release 11 2016 Seite 31 von 31 Software Project Version Licenses FreeRTOS 7 0 0 GPL2 MODIFIED BY the FreeRTOS exception ASF 3 21 0 3 18 1 Atmel ASF license lwIP 1 4 BSD axTLS 1 5 2 BSD ...

Reviews: