INSTALLATION & OPERATING DATA

A T E X

M 2 / M 1

GROUP I

INTRINSICALLY

SAFE

6 PRECAUTIONS

  Ensure that all covers on Exd housings and their fixing devices are properly secured in compliance with

statutory Exd regulations before switching on the input supply.

Never  remove  the cover of  an Exd housing whilst the input supply is connected. Isolate elsewhere
before removing the cover in accordance with statutory regulations.

The housing of all power supplies must be securely earthed in compliance with statutory regulations.

Carry out a current consumption audit to ensure that the maximum current loading of the power
supply is not exceeded.

Ensure that the installation of the power supply, particularly with regard to the
connecting cables, complies with the certification parameters (section 7).

Exd housings must be inspected and maintained regularly in accordance with statutory regulations.

  Use only the correct Trolex replacement fuses (section 7).

Do not substitute any form of equivalent or linking device.

  The TX6630 Series Exi Power Supply must be mounted in an approved Exd housing when located in a

hazardous area.

  All cables entering the Exd housing must be terminated with suitable Exd certified cable glands.

  The cabling between the Power Supply and other approved intrinsically safe devices must comply with

the cable parameters specified in the appropriate Ex certification of the device.

  Never connect two power supplies in parallel, or employ external circuitry that results in two Intrinsically

Safe Power Supplies circulating in one system. This will contravene the limits of Intrinsic Safety.

  Where an Intrinsically Safe Power Supply is fitted with auxiliary

Intrinsically Safe isolating relays, all the relay coils are powered
from a common Intrinsically Safe source.

  If an ac input fuse is ruptured at any time, it can be replaced. It is recommended however, that a full

investigation is carried out to try to establish the cause of the failure as this could indicate potentially
dangerous external conditions.

It is good practice to check the condition of the mating flame path surfaces on the Exd chamber
cover whenever it is removed.

Five x M25 threaded cable entries are provided on the underside of the Exd chamber for connecting
the incoming Power Supply and for connections to relay contacts if these are fitted.

Approved Cable Glands:
Hawke:  650 series Compound Filled M25 Thread
Hawke:  650 series Compound Filled M20 Thread (when used with a M25/M20 reducer).

Approved Thread Reducers:
Hawke:  476/R, M25/M20 Thread

  All unused cable entries MUST be blanked off with an APPROVED STOPPING PLUG.

Approved Stopping Plugs:
Hawke:  475, M25 Thread

  The requirements of the Exd certification of the TX6620 Series Intrinsically Safe Power Supply demand that

electrical

isolation must be provided in the mains Power Supply feed. The isolation should be  mounted

adjacent to the Power Supply.

The metal housing of the Power Supply, should be earthed in compliance with local regulations.

  Ensure that the mating faces of the Exd chamber cover are clean and free from inclusions before the

cover is replaced. It is permissible to use copper grease on the mating faces to protect against
corrosion and moisture ingress.

Refer to Section

 7

Refer to Section

 7

I.S.

Source

RL1 

RL2 

RL3 

RL4

T

T

 X

X

 9

9

 1

1

 3

3

 0

0

  s

s

  e

e

  r

r

  i

i

  e

e

  s

s

ISSUE D 06/14

7/12

Summary of Contents for TX6620

Page 1: ...NFORMITY CHECK 3 4 DIMENSIONS AND CONNECTIONS 4 5 ISOLATING RELAYS 5 6 PRECAUTIONS 7 7 APPROVALS AND CERTIFICATION 8 DESIGNED TO CONVERTACSUPPLY VOLTAGEINTOA STABILISEDAND REGULATEDI S SOURCE FOR SUPP...

Page 2: ...may be fitted and wired into an existing Exd housing specific system certification may also be required or into a standard protective housing that is in a SAFE AREA The TX6620 Series version is the T...

Page 3: ...ge rating of the coils correct If isolating relays are fitted are the relay parameters suitable for the load being switched 3 CONFORMITY CHECK 110V ac 230V ac 0 5A 1 5A E Ex xd d or S Sa af fe e A Ar...

Page 4: ...110Vac or 230Vac 0V V Exi Chamber ExdChamber 310 0 50 0 210 0 Centres 320 0 304 0 Centres 8 0 8 9 0 Fixing Holes Earth Stud 5 M25 Exd Gland Entries Exi Chamber Exd Chamber 38 0 304 0 Centres 122 0 2...

Page 5: ...24 Ohms TX6636 12V dc 0 5A 10A 230V ac 580 Ohms ALL DIMENSIONS IN MM V 0V MainsInput 110Vacor230Vac L E N V RL2 V RL3 V RL4 V RL1 RL2 RL3 RL4 RL1 RL2 RL3 RL4 Com NO NC ComNO NC Com NO NC Com NONC RL1...

Page 6: ...RELAYS Supplied loose ready for fitting and wiring TX6636 19 INTRINSICALLY SAFE POWER SUPPLY CHASSIS with RELAYS Supplied loose ready for fitting and wiring Nominal O P Max O P Relay Contact Voltage C...

Page 7: ...the limits of Intrinsic Safety Where an Intrinsically Safe Power Supply is fitted with auxiliary Intrinsically Safe isolating relays all the relay coils are powered from a common Intrinsically Safe s...

Page 8: ...ply Chassis Um 375V peak Uo 14 4V dc Io 2 37A Co 20uF Lo 100uH Po 9 84W T T X X 9 9 1 1 3 3 0 0 s s e e r r i i e e s s 7 5 Special Conditions for Safe Use TX6620 The electrical isolation must be prov...

Page 9: ...vents that may affect polymeric materials Suitable Precautions e g regular checks as part of GB B Be ed di in ng gu un ng ge en n f f r r d di ie e I In ns st ta al ll la at tiio on n i in n e ex xp p...

Page 10: ...r re ek kk ki in ng g o op p i in ns st ta al ll la at tiie es s v vo oo or r g ge ev va aa ar rlli ij jk ke e r ru ui im mt te en n n na aa ar r E Eu ur ro op pe es se e A AT TE EX X R Ri ic ch ht tl...

Page 11: ...IFICATION continued N No or rm me e s sp pe ec ci if fi ic ch he e a al ll le e i in ns st ta al ll la az ziio on nii i in n z zo on ne e a a r riis sc ch hiio o r riif fe er riim me en nt to o D Di i...

Page 12: ...life endorsed by our commitment to recycling and recovery All packaging materials are carefully selected to be bio degradable or re cycleable where possible All plastic materials are identified for re...

Reviews: