Trol Systems MCU-04-115 Installation Manual Download Page 1

Installation guide for part number:

MCU-04-115

T6

T6

T6

T6

T6

T6 is a trade name of Trol Systems Inc.

TSI reserves the right to make changes to the information contained in this manual without notice.

publication MCU115- rev:5 | © 2003 TSI All rights reserved | printed in USA

Main

Control

Unit

Specifications for: MCU-04-115

Power Requirements:

115VAC @ .02A, 50/60Hz w/1000v magnetic isolation

Outputs:

4 normally open relay contacts unprotected, no leakage current
5Amps @ 230VAC ( resistive load ), 250 VA ( inductive load ).
Response time: 10ms operate / 5ms release
Rated life: 5 million ( mech ) / 200,000 @ 3A ( resistive load )

Inputs:

6 self powered, 12-14 VDC @ 10ma. w/ 1000v optical isolation.
Maximum leakage of input device: 0.5ma
Response time: all are factory set at 10ms, the user may change
any input to between 0 to 255ms using the Setup Menu.

Auxiliary Supply:

10 - 14vdc @ 100ma., thermal overload protected.

Physical:

Size

2.9” ( 75mm ) x 2.2” ( 55mm ) x 4.3” ( 110 mm )

Mounting

DIN rail or panel ( with two #6 screws )

Weight

10 oz. ( 284 grams )

Temp

0 - 140

°

F, 90% r. humidity ( no condensation )

Origin

Designed and assembled in the USA.

Communication Ports:

Expansion

Twin RJ-11, IIc bus @ 100khz max.

PC Prog.

3.5mm, RS-232C @ 19200 Hi / 9600 Lo

Visit our web site at www.trolsystems.com for

latest information about the T6 control system.

Reviews: