background image

Exe Inclusive Bar Mixer Shower

2

INTRODUCTION

This book contains all the necessary fitting and 
operating instructions for your mixer shower. 
Please read them carefully and read through 
the whole of this book before beginning your 
installation.
The shower installation must be carried out by 
a suitably competent person and in sequence of 
this instruction book.
Care taken during the installation will give a long 
and trouble free life from your mixer shower.

SITE REQUIREMENTS

The installation must be in accordance with 
water supply (water fittings) regulation 1999 
and/or local Bylaws.

Water Pressure Requirements

Running water pressure:

 

Low pressure* 

-  0.1 bar min.

   

  1.0 bar max.

  High pressure 

-  0.5 bar min.

   

  5.0 bar max.

Maximum static water pressure:

 Low & High pressure 

-  10 bar

*This mixer shower is designed for high pressure 
systems found in the UK, but can be installed 
with low pressure gravity water systems with 
reduced flow rates.
For effective operation of the internal seals, the 
maximum static pressure must not be exceeded.

Pressure Reducing Valve

On sites where the running pressure is above 5 
bar, the use of a suitably sized pressure reducing 
valve fitted in the cold mains supply pipework 
can provide nominally equal pressures at the 
mixer shower.

Water Minimum Flow Rate

For best performance within the specified running 
pressure range a minimum flow of 8 litres per 
minute should be available to both inlets.

Water Temperature Requirements

Recommended maximum: 

= 65°C

Minimum hot water temperature:  = 55°C
Maximum cold water temperature:  = 25°C

NOTE:

 Valves operating outside these conditions 

cannot be guaranteed by the Scheme to operate 
as Type 2 valves.
A stored water temperature of 60°C is 
considered sufficient to meet all normal 
requirements and will minimise the effects of 
scale in hard water areas.

Water Temperature Adjustment and 
Thermal Safety

The mixed water temperature can be adjusted 
from cold through to a top limit which must 
be preset during installation with full anti-scald 
protection throughout the range (35°C to 40°C) 
providing the hot water temperature at the inlet 
remains 10°C above the outlet temperature.
Should there be a loss of flow to either incoming 
supply then water from the shower will stop or 
be reduced until both supplies are restored.

SAFETY WARNINGS

a. 

DO NOT

 choose a position where the shower 

could become frozen.

b. 

DO NOT

 connect this mixer shower to any 

form of tap or fitting not recommended by 
the manufacturer.

c. 

DO NOT

 allow the inlet pressure or flow 

rates to operate outside the guidelines laid 
out in ‘site requirements’.

d.  

DO NOT

 connect the mixer shower to a 

gravity hot supply and a mains cold supply or 
vice versa.

Summary of Contents for EXE LEVER

Page 1: ...BY TEL 024 7637 8321 INSTALLATION AND OPERATING INSTRUCTIONS Please read this book thoroughly and familiarise yourself with all instructions before commencing installation and keep it for future refer...

Page 2: ...ADJUSTMENT RANGE 11 ADJUSTING THE MAXIMUM TEMPERATURE SETTING 11 OPERATING THE SHOWER 12 DIMENSIONS 13 APPROVALS 14 TMV2 REQUIREMENTS 12 MONTH VERIFICATION 14 PRODUCT FLOW RATES 14 MAINTENANCE 15 FAUL...

Page 3: ...Exe Inclusive Bar Mixer Shower 1 Fig 1 A Thermostatic bar mixer valve B Dogleg connector X2 C Cover trim X2 B MAIN COMPONENTS C C A...

Page 4: ...t the mixer shower Water Minimum Flow Rate For best performance within the specified running pressure range a minimum flow of 8 litres per minute should be available to both inlets Water Temperature R...

Page 5: ...ugh before fitting Commercial Applications It is recommended that for all commercial applications easily accessible in line filters are used to aid maintenance Hard Water Areas a If it is intended to...

Page 6: ...boost pressures as shown please refer to the pump installation guide to establish the minimum head requirements for automatic operation of the pump Hot water cylinder Cold supply Hot supply Alternativ...

Page 7: ...or systems with no cold water take off after the appliance reducing valve it will be necessary to fit an additional drop tight pressure reducing valve when the mains pressure is over 5 bar The drop ti...

Page 8: ...ar running An expansion vessel MUST be fitted and regularly maintained to ensure the unit is not damaged by excess pressures This may already be installed externally or internally within the thermal s...

Page 9: ...shower area having decided on the position of the shower and direction of pipe entry for example rising falling or rear entry The hot and cold water pipes should be securely attached within the wall...

Page 10: ...ood the wall and complete the tiling NOTE It is advised to use a suitable sealer around the variable connector where it enters the wall to stop water ingress fig 9 Screw the supplied cover trims onto...

Page 11: ...clockwise until it stops NOTE The flow control graphic styles of this may vary should be positioned so that the front edge of it is at the 12 o clock position The remainder of the graphic should run t...

Page 12: ...in the requirements as stated on page 2 Make sure the temperature control right hand side is at the maximum temperature setting WITHOUT operating the maximum temperature override button Allow the show...

Page 13: ...temperatures must never exceed 46 C at terminal fitting The British Burns Association recommends 37 to 37 5 C as a comfortable bathing temperature for children In premises covered by the Care Standar...

Page 14: ...ops flowing fig 15 To adjust the water temperature rotate the temperature control right hand side clockwise for a cooler shower or anti clockwise for a hotter shower fig 16 To overcome the maximum tem...

Page 15: ...Exe Inclusive Bar Mixer Shower 13 290 00 1 2 BSP 180 00 150 00 3 4 BSP 4 0 5 0 56 25 DIMENSIONS All dimensions regarding the product and installation are approximate...

Page 16: ...ing then the valve is working correctly and no further service work is required If there is a residual flow during the commissioning or the annual check this is acceptable providing the temperature of...

Page 17: ...a Initially check the filters for debris once every three months and clean if necessary b Perform a thermal shut off test every three months and check the maximum temperature setting See the Commissi...

Page 18: ...supply blocked or restricted 2 6 Flow regulator not fitted HP systems only 3 1 Flow regulators not fitted 1 1 1 Refer to the Commissioning section 1 2 1 Reposition temperature control knob 1 3 1 Repo...

Page 19: ...t the inlet filters Clean if necessary 4 3 1 Turn off the shower and consult a suitably competent plumber 4 4 1 Clean shower head 4 5 1 Reduce the simultaneous demand 4 5 2 Make sure stop service valv...

Page 20: ...ent of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verify your requirements using the Information cont...

Reviews: