CONFIGURATION
DEVICE SETTINGS
DEVICE THRESHOLDS
Threshold
Value(s)
Description
Overload Alert Lvl.
• Enter: 5-105%
(factory setting is 100%)
Sets the UPS output load percentage before
an overload alert is sent.
Conf. Fault Action
(UPS response to
fault)
• Go to bypass (factory setting)
• Go to standby
Sets the UPS response to fault conditions
that require the UPS to exit double-
conversion mode. GO TO BYPASS option
maintains AC output (so long as input
voltage is within bypass high/low limits). GO
TO STANDBY option causes the UPS to turn
off output AC in response to fault conditions.
Bypass Low Limit
• Enter: -5% to -20%
(factory setting is -15%)
Specifies the lowest acceptable input
voltage for bypass operation.
Bypass High Limit
• Enter: +5% to +20%
(factory setting is +10%)
Specifies the highest acceptable input
voltage for bypass operation.