The HC350S and HC350S1 series of hospital cart power modules are designed to 

provide AC voltage output power from either utility provided AC input voltage or from 

inverting 12VDC power from a sealed lead acid battery.  To ensure proper operation the 

following guidelines should be observed: 

1. The power module can support AC loads up to a maximum of 400VA or 300W.

2. The power module charger is intended to be used with a 12V sealed lead acid

absorbed glass mat (AGM) battery with a 33AH to 66AH

 

rating.  Batteries rated

at less than 33AH are not recommended since the charger current of 12A would

reduce the battery cycle life of smaller batteries.

3. Adequate provision for airflow needs to be provided at both the inlet and outlet

vents of the power module.  There should be at least 0.5 inches of clear space

on the fan end and on the vented end of the power module.  A baffle or air

deflector is recommended at the fan end so that the air intake is raised at least 6

inches above floor level to prevent dust accumulation inside the power module.

4. The power module may be mounted in any orientation.  Four 8-32 threaded

inserts are provided on the surface with the AC input cord to facilitate mounting.

5. The AC voltage input and output connections are made with user supplied cables

to the IEC input and output connectors on the power module.  Use only with

approved plug/cord sets according to the equipment electrical ratings.

  

No

external fusing is needed since safe operation is assured by internal non-

replaceable 10A fuses.  However, if a customer wishes to prevent the internal

fuses from blowing in the event of an extreme overload, then an external fuse or

circuit breaker rated at 6A to 10A (120VAC models) or 3A to 5A (230V models)

should be provided on the AC voltage input.

6. The 12V battery input is made with a user supplied cable to the Anderson DC

connector on the power module.  Proper polarity must be observed.  The

recommended wire size is 8 AWG in order to keep the voltage drop in the cable

to less than 0.1V.  The length of cable between the battery and the power

module should be less than 30 inches.  A user supplied 40A to 50A automotive

style fuse is required in the positive lead of the battery (within 18 inches of the

battery positive terminal).

7. Additional bonding is needed to connect the battery negative terminal to the case

of the power module.  The wire (or metal frame of the cart) should be short (less

than 18 inches) and preferably of the same gauge as the other battery wires