Triple Solar assembly instruction PVT heat pump panels March 2020
Pipe diameters of source pipes
The pipe diameter is largely dependent on the power of the heat pump. In addition, the total length of the
pipework, the number of bends and the height difference between the heat pump and the panel field are
important. The table below provides a guideline for sizing the pipe diameters of source pipes. This concerns
the minimum diameters of the pipes running to and from the panel field, including the fittings.
After the junctions in the panel field, pipe diameters can be reduced.
Power heat pump
minimum internal diameter of the
pipes running to and from the panel
field
6 kW to 8kW
26 mm
8 kW to 15kW
32 mm
15kW to 28kW
41 mm
28kW to 50kW
51 mm
Hydraulic plan
•
Fit a 3 bar pressure relief valve or use the supplied expansion vessel connection group (3 bar
pressure relief valve with automatic air vent).
•
The filter valve (supplied with Nibe heat pumps) must always be placed in front of the
thermostatic mixing valve (Esbe mixing valve) to prevent the valve from becoming dirty.
•
The filter valve (supplied with Nibe heat pumps) with the smaller diameter must be placed in the
cold side of the central heating circuit.
•
Preferably do not place taps between the roof and the expansion vessel. This to avoid mistakes
during maintenance (See chapter 'Maintenance' for an explanation).
•
For larger fields it is wise to place a valve per row so that each row can be vented.
Figure 8.4-a general hydraulic plan Triple Solar system