1 Description

The TR-INT50W Internal Amplifier can fit inside the Triga 

Series cabinet. It is used to amplify the audio message for distri-

bution throughout the facility for the Emergency Communication 

System.

1.1  Compatibility

TR-2100

TR-2100ECS

2 Installation Board Layout and 
Mounting

Figure 1 shows the TR-INT50W front view board layout.

Figure 1  TR-INT50W Front View 

2.1 Mounting the TR-INT50W 

To mount the TR-INT50W, refer to the following steps.
1. Remove the AC power and disconnect the backup batteries

from the main control panel.

2. To mount the TR-INT50W inside the FACP cabinet under

the main board, align the board with the mounting holes.

3. Secure the board to the enclosure with the supplied screws.

See Figure 2.

Figure 2 shows the TR-INT50W board mounted in the FACP 

cabinet under the main control board.

.

Figure 2  TR-INT50W mounted in the FACP Cabinet under the 

Main Control Board

4. When you mount the TR-INT50W in the ECS cabinet that

contains a ECS-NVCM, it is necessary to mount the TR-

INT50W on the right side of the control board.
To do this, use the ECS-AMPMT mounting kit (ordered

separately).

5. Mount the ECS-AMPMT into the cabinet using the six

supplied screws. Position the board with the “Top” side up.

(See Figure 3).

6. Secure the TR-INT50W onto the six standoffs, ensure the

two coil parts are placed at the top, and on the right side of

the ECS-AMPMT. See Figure 3 for the coil position.

Figure 3  Mounting the TR-INT50W

3 Specifications

NOTE:

The installation and wiring of this device must be 

done in accordance with the NFPA 72 and local 

ordinances.

NOTE:

For more information, refer to the FACP 

Installation Manual or Triga Series, ECS Manual 

PN:LS10262-002TR-E.

SBUS

VBUS

DIP Switch

Power

IN1 / OUT1

Standby Current:

52mA

TR-INT50W only 

Alarm Current:

@ 25V 275mA; @ 70V 310mA

Full Alarm load current:     @ 25V 2840mA; @ 70V 2900mA     

ECS-AMPMT

holes

“TOP”

Cabinet 
with the 
ECS-
AMPMT 
Installed

Standoffs

Coils to top

TR-INT50W 

installed 

using 

ECS-

AMPMT