PN LS10255-002TR-E:A   02/03/21   ECN: 151608

TR-5865-3 and TR-5865-4 LED Annunciator

 Product Installation Document

TRIGA Life Safety Systems, LLC

7600 Olde Eight Rd, Hudson, Ohio, 44236-1057
Tel: +1 330-577-5199, Email: [email protected] 

1 Description

The TR-5865-3 and TR-5865-4 are LED Annunciators that provide 
thirty programmable LED’s (fifteen LEDs light red and fifteen LEDs 
light yellow). The TR-5865 annunciator connects to the panel via the 
SBUS.

1.1  Compatibility

The TR-5865-3 and TR-5865-4 are compatible with the following Triga 
Series, Fire Alarm Control Panels (FACPs). For information on the pro-
gramming, the addressing and the wire connections, refer to following 
FACP Installation Manuals. The documents are located on the Triga 
Series website, www.trigaglobal.com.

1.2  Specifications

The specifications are as follows.

2 Mounting the TR-5865-3

The TR-5865-3 mounts into a standard 3-gang electrical box. To mount 
the TR-5865-3, refer to the following steps.
1.

Make sure that the TR-5865-3 is properly wired to the control

panel. See Figure 2.

2.

Place the TR-5865-3 into the 3-gang electrical box. See Figure 1.

.

Figure 1 TR-5865-3 Mounting

3.

Place the cover plate over the top of the TR-5865-3 and align the

holes. See Figure 1.

4.

Insert the six cover plate screws into the six screw holes on the 3-

gang electrical box.

5.

Secure and tighten the six screws so that the cover plate fits firmly

against the TR-5865-3 and the electrical box.

2.1 Mounting the TR-5865-4

The TR-5865-4 mounts into a standard 4-gang electrical box. To mount 
the TR-5865-4, refer to the steps in Section 2. 

3  Wiring the TR-5865-3 or TR-5865-4

Terminate the wiring as shown in Figure 2. For wiring terminal connec-
tions, refer to Table 1.

Figure 2 TR-5865-3 or TR5864-4 Connection to the FACP

Document

Document Part Number

TR-2100ECSR Manual

LS10143-003TR-E

TR-RPS1 Manual

LS10259-002TR-E

Triga ECS Manual

LS10262-002TR-E

• Standby Current:

 35mA

• Alarm Current:

145mA

• Max. Line Resistance:      50

Ω

• Max. Voltage

24VDC

• Operating Temperature    0° to 49° C (32° to 120° F)
• Indoor Use Only

cover plate

5865-3

3-gang

electrical box

cover 

plate

screw

NOTE:

The TR-5865-4 uses 8 cover plate screws.

NOTE:

The installation and wiring of these devices shall be 

performed in accordance with the NFPA 72 and the local 
ordinances.

TR-5865-3 & TR-5865-4 

Terminals

FACP Terminals

Label

B

B

A

A

S+

+

S-

-

Table 1   Wire Terminal Connections

supervised

power-limited