background image

luxCONTROL

DALI basicDIM DGC

Product Manual

Summary of Contents for DALI basicDIM DGC

Page 1: ...luxCONTROL DALI basicDIM DGC Product Manual ...

Page 2: ...escription 6 4 Installation 7 5 Functions 10 5 1 Basic functions 10 5 2 Constant light control 23 5 3 Presence control 27 5 4 Remote control 31 6 Room profiles 32 6 1 Room profile 1 Individual room 32 6 2 Room profile 2 Classroom 35 6 3 Room profile 3 Corridor 38 6 4 Room profile 4 Restroom 41 6 5 Room profile 5 Free standing luminaire default 44 7 Status information 47 7 1 Green light Normal oper...

Page 3: ...ctions is available on our home page at http www tridonic com com en operating instructions asp 1 1 Copyright This documentation may not be changed expanded copied or passed to third parties without the prior written agreement of TRIDONIC GmbH Co KG We are always open to comments corrections and requests Please send them to info tridonic com 1 2 Imprint Tridonic GmbH Co KG Färbergasse 15 6851 Dorn...

Page 4: ...o the product 2 2 Dangers associated with the operation of the system WARNING Improper use could result in injury malfunction or damage to property It must be ensured that the operator informs every user of existing hazards DANGER Danger of electrocution Disconnect the power to the entire lighting system before working on the lighting system CAUTION Risk of damage caused by condensation Prior to c...

Page 5: ...the basicDIM DGC module is used in the basic application the CH2 can be used as control channel for controlling subordinate basicDIM DGC modules basic connection so that the controlling and the subordinate basicDIM DGC modules can be programmed and allocated to groups using the masterCONFIGURATOR software Every single basicDIM DGC module can be allocated to only one group and respond to the presen...

Page 6: ...sor Remote control Remote control DALI basicDIM DGC basicDIM DGC Sensor 5DPI 14f inbuilt basicDIM DGC Sensor 5DPI 14 rc remote basicDIM DGC Programmer REMOTE CONTROL IR6 28000920 28000933 28000934 28000646 28000647 Supply 230 V AC 50 60 Hz _ 1 relay output L max 500W 200VA _ T1 T2 Terminals for the connection of two local 230 V keys _ DALI IN input _ Sensor connection for up to 4 basicDIM DGC sens...

Page 7: ...Product manual basicDIM DGC 07 2018 1 9 en Installation c 7 48 ...

Page 8: ...ram basicDIM DGC with DALI PS1 2 Use only in combination with DALI Repeater 86458401 and one of the following DALI supplies This combination can be used on CH1 and CH2 DALI PS1 24034323 200 mA max 100 additional devices _ DALI PS2 28000876 240 mA max 120 additional devices _ ...

Page 9: ...e exceeded 100 m 2 _ If CH2 is used as link line the maximum cable length must not exceed 100 m at 1 5 mm 2 _ Any number of push to make switches may be connected in parallel to the inputs _ Do not connect standard switches to the input _ Please ensure that the detection range of the sensor lies in the lighting area of the controlled luminaires _ Heaters fans printers and copiers located in the de...

Page 10: ...LI CH2 eD Normal operation The eD parameter QUERY TYPE CONTROL NUMBER checks whether an additional basicDIM DGC is connected to CH2 which corresponds to basic configuration If this is the case the DALI IN port will be disabled Basic functions _ Constant light control by means of ambient light sensor _ Presence based control by means of PIR motion sensor or presence detector _ Remote control via an...

Page 11: ...ors If the DGC is moved to group 1 for example it will still send its own presence as Broadcast by default If there is an MSensor in the same installation for example in group 2 then group 2 will be triggered by the Broadcast signal sent from the DGC To avoid this behaviour make sure that the DGC is programmed to send its presence to the group that it is assigned to in this example group 1 ...

Page 12: ...mmands CAUTION By using the DGC in basic configuration additional DGCs connected to CH2 DALI IN interface will be deactivated To activate the DALI IN interface DALI again proceed as follows RESET _ STOREACTUALLEVELINTHEDTR _ STORETHEDTRASMAXLEVEL _ STORETHEDTRASMINLEVEL _ STORETHEDTRASFADETIME _ ADDTOGROUP _ REMOVEFROMGROUP _ STOREDTRASSHORTADDRESS _ ENABLEWRITEMEMORY _ TERMINATE _ DATATRANSFERREG...

Page 13: ...sicDIM DGC 07 2018 1 9 en Functions c 13 48 Reaction to DALI control commands at the DALI IN interface DIRECT ARC POWER CONTROL DAP _ OFF _ UP Down _ RECALL MAX LEVEL _ RECALL MIN LEVEL _ ON AND STEP UP _ GO TO SCENE _ ...

Page 14: ...o DALI QUERY MISSING SHORT ADDRESS According to DALI QUERY VERSION NUMBER According to DALI QUERY CONTENT DTR According to DALI QUERY DEVICE TYPE According to DALI QUERY PHYSICAL MINIMUM LEVEL According to DALI QUERY CONTENT DTR1 According to DALI QUERY CONTENT DTR2 According to DALI QUERY ACTUAL LEVEL is Current nominal value of output channel 1 is answered even if output channel 1 0 and is outpu...

Page 15: ...ighting control is reactivated if the luminaire switches on again automatically when motion is detected or if it is switched off and on manually The function can be edited with the basicDIM DGC Programmer or the masterCONFIGURATOR software see Reference list at the end of this document 2 x short press Stores the currently measured light value as new setpoint of the lighting control luminaire ackno...

Page 16: ...standing luminaire the relay operating modes Standby and OnlyOFF are used The masterCONFIGURATOR software allows to enable or disable the relay profiles as well see Reference list at the end of this document 5 1 7 Presence detector Depending on the profile used different operating modes are preprogrammed for the presence detector These can be changed using the basicDIM DGC Programmer or the master...

Page 17: ...or a DAP command 0 Recall Max Recall Min the Run on time is started Response to neighbourhood function If as response to the neighbourhood function the presence value was set the run on time is started Response to scene commands Responses to scene commands are described at Scenes p 22 5 1 9 Switch off delay Time for which the absence value is maintained if no movement is detected The switch off de...

Page 18: ... any presence detected the presence detector is enabled again If the sensor detects presence during the Manual Off delay the delay time will start all over again The manual off delay can only be changed using the masterCONFIGURATOR software see Reference list at the end of this document 5 1 13 Lighting control Lighting control is started via the Auto key of the basicDIM Programmer or REMOTECONTROL...

Page 19: ...on the sensor by a slowly flashing green status LED By default this function is disabled but it can be enabled using the masterCONFIGURATOR software see Reference list at the end of this document Light control incl brightout activated for CH1 CH2 is not illuminated controlled REMOTECONTROL IR6 press the key for 3 s _ basicDIM DGC Programmer press the key for 3 s _ masterCONFIGURATOR software _ ext...

Page 20: ...If presence is reported by other groups the light level will switch to presence value Switched on If presence is reported by other groups the light level will switch to absence value 5 1 17 Momentary action switch inputs Depending on the profile used the momentary action switch inputs control different functions Symbol Description Momentary action switch 1 Momentary action switch 2 Display of outp...

Page 21: ...l basicDIM DGC 07 2018 1 9 en Functions c 21 48 5 1 18 Basic functions Symbol Description Switching on If the DGC module has been switched on via ON lighting control is disabled Switching off Dimming up Dimming down ...

Page 22: ...nd is decisive Important note If for example CH1 is programmed with 0 and CH2 with MASK then the state of CH2 before the scene command is decisive Response of the relay to scene commands The relay does not respond to scene commands when it is in standby mode If the relay is programmed with MASK then the state of the relay before the scene command is decisive for example if the relay is programmed ...

Page 23: ...onger than the specified delay time the luminaire group is switched off by the DALI basicDIM DGC This also applies in cases where motion is detected in the room The luminaire group is switched on again as soon as the measured illuminance falls below the brightness setpoint The Constant light control function ensures that the illuminance in the room remains constant and changes due to variable amou...

Page 24: ... detection angle of the sensor and the height at which it is mounted Calculating the diameter x1 tan x1 h x2 tan x2 h y tan y h Typical example values of detection area Height h m ø x1 m ø x2 m ø y m 1 7 1 3 0 7 1 0 2 0 1 6 0 8 1 2 2 3 1 8 0 9 1 3 2 5 2 0 1 0 1 4 2 7 2 1 1 1 1 6 3 0 2 3 1 2 1 7 3 5 2 7 1 4 2 0 ...

Page 25: ...y is crucial 1 In order to be able to control ambient lighting properly the sensor must be able to detect the light from the controlled luminaires completely 2 If the sensor is directly exposed to other light sources this falsifies the results obtained and the reflected artificial light and daylight can no longer be detected correctly Position the sensor so that the sensor s detection area lies wi...

Page 26: ...cuits to affect one another and this may lead to false results Position the sensor so that it is not directly exposed to sunlight _ Make sure that the detection area of the sensor lies within the room _ Make sure that the sensor is far enough away from any window area _ Make sure that any glare or sunlight reflected by shiny glass or metal surfaces cannot hit the sensor _ Position the sensors so t...

Page 27: ...s of a pattern of various measurement fields The following conditions must be met in order for an object to be detected reliably The diameter of the detection area depends on the detection angle of the sensor and the height at which it is mounted The mounting height also has an effect on the sensor s accuracy I NOTICE The presence based control of the basicDIM DGC sensors reacts to moving thermal ...

Page 28: ... 2 7 4 9 3 0 5 4 3 5 6 3 4 0 7 2 Up to 2 m mounting height presence is detected and over 2 m motion is detected _ I NOTICE The recommended maximum room height is 3 m for office applications and 4 m for corridor applications For presence detection it is vital that arm movements etc can be detected Position the sensor on the ceiling so that the room user s hands are located in the centre of the dete...

Page 29: ... run on time expires mC1 and Pr2 3 Fade time 0 7 90 5 s default 5 6 s Time during which the luminous intensity is faded from the presence value to the absence value mC1 4 Switch off delay 0 s infinite default depending on profile Time during which the absence value is held before the lighting is switched off Depending on the profile selected the switch off delay may have different values or may no...

Page 30: ...l basicDIM DGC 07 2018 1 9 en Functions c 30 48 B Absence value 1 100 default depending on profile Luminous intensity when there is no person present mC1 and Pr2 mC masterCONFIGURATOR Pr basicDIM DGC Programmer 1 2 ...

Page 31: ...used in combination with a basicDIM DGC sensor it can be controlled with the following remote controls To get more information about these remote controls follow the link beside the product image basicDIM DGC PROGRAMMER 28000646 www tridonic com qrDGCProg REMOTECONTROL IR6 28000647 www tridonic com qrIR6 ...

Page 32: ...room 6 1 1 Brief description Typical setting Two illumination areas e g CH2 windows area CH1 rest of the room two switches T1 T2 motion sensor s Control Switch 2 T2 controls the lighting of the windows area CH2 switch 1 T1 controls the lighting of the rest of the room CH1 6 1 2 Available commands ...

Page 33: ...inaires at both outputs flash twice pause for 5 s between double clicks T2 effective range Only Output 2 T2 short press ON and OFF T2 long press dimming T2 double click Saving enabled Luminaires at both outputs flash twice pause for 5 s between double clicks Relays standby Constant light control BrightOUT enabled dimming out after 10 minutes Constant light control output 1 automatic Constant light...

Page 34: ...rol run on time 10 min Presence control absence value 10 Presence control switch off delay 1 min Presence control Fadetime 5 7 sec Presence control manual OFF delay 10 min Presence control signal exchange disabled no response to presence of other devices Output 1 operating mode DALI Output 2 operating mode DALI no network master ...

Page 35: ...etting Three illumination areas windows area rest of the room separate presentation area two switches motion sensor s Control area Switch 1 controls the lighting of the windows and the rest room of the room together ratio of the two dimming levels remains the presentation area same button 2 controls the 6 2 2 Available commands ...

Page 36: ... Presence control run on time 20 min Presence control absence value 0 Presence control switch off delay 0 min Presence control Fadetime 5 7 sec Presence control manual OFF delay 10 min Presence control signal exchange disabled no response to presence of other devices Output 1 operating mode DALI Output 2 operating mode DALI no network master ...

Page 37: ...trol run on time 20 min Presence control absence value 0 Presence control switch off delay 0 min Presence control Fadetime 5 7 sec Presence control manual OFF delay 10 min Presence control signal exchange disabled no response to presence of other devices Output 1 operating mode DALI Output 2 operating mode DALI no network master ...

Page 38: ...ing One illumination areas switches motion sensor s Control all the luminaires Different dimming levels can be defined for presence detection in another room Switches control the lighting of neighbourhood function for presence detection in the corridor itself and for the absence of any presence detection 6 3 2 Available commands ...

Page 39: ...ing T1 double click Saving disabled T2 effective range Output 1 and Output 2 T2 short press Only ON T2 long press dimming T2 double click Saving enabled Relays standby Constant light control BrightOUT enabled dimming out after 10 minutes Constant light control output 1 automatic Constant light control output 2 automatic no offset 0 Presence control mode ON OFF Presence control run on time 1 min Pr...

Page 40: ...nce control switch off delay never OFF Presence control Fadetime 5 7 sec Presence control manual OFF delay 1 min Presence control signal exchange disabled no response to presence of other devices Output 1 operating mode DALI Output 2 operating mode DALI no network master ...

Page 41: ...g Two illumination areas sink and mirror area toilet area two switches motion sensor s Control switch lighting of the toilet area Switch 1 controls the lighting of the sink and mirror area 2 controls the In connection with presence detection different dimming levels can be defined for the two lighting areas 6 4 2 Available commands ...

Page 42: ...T1 double click Saving is blocked T2 effective range Relay T2 short press Only ON only possible if Output 1 is ON T2 long press disabled T2 double click Saving is blocked Relays only OFF Constant light control BrightOUT enabled dimming out after 10 minutes Constant light control output 1 automatic Constant light control output 2 manual Presence control mode ON OFF Presence control run on time 20 m...

Page 43: ...sence control switch off delay 0 min Presence control Fadetime 5 7 sec Presence control manual OFF delay 1 min Presence control signal exchange disabled no response to presence of other devices Output 1 operating mode DALI Output 2 operating mode DALI no network master ...

Page 44: ...Brief description Typical setting Two illumination areas direct and indirect lighting two switches motion sensor s Control switch Switch 1 controls direct lighting 2 controls indirect lighting If no presence is detected the free standing luminaire is switched off completely to avoid stand by losses 6 5 2 Available commands ...

Page 45: ... Saving enabled Luminaires from output 1 will flash twice T2 effective range Output 2 T2 short press ON and OFF T2 long press dimming T2 double click Saving enabled Luminaires from output 1 will flash twice Relays standby Constant light control BrightOUT enabled dimming out after 10 minutes Constant light control output 1 automatic Constant light control output 2 manual Presence control mode ON OF...

Page 46: ...ence value 10 Presence control switch off delay 1 min Presence control Fadetime 5 7 sec Presence control manual OFF delay 10 min Presence control signal exchange disabled no response to presence of other devices Output 1 operating mode DALI Output 2 operating mode DALI no network master ...

Page 47: ...werOn 1 x short impulse Presence detected 2 x short impulse Confirmation of infrared reception 7 2 Orange light Maintenance Status indicator Meaning Normal flashing Addressing initialization or identification in progress Slow flashing Firmware update in progress 7 3 Red light Error Status indicator Meaning Cyclic rapid flashing with pause Short circuit on output 1 or output 2 Rapid flashing Jammed...

Page 48: ...download technical basicDIM_DGC_PROGRAMMER_en pdf _ Parameter settings REMOTECONTROL IR6 http www tridonic com com en download technical REMOTECONTROL_IR6_en pdf _ Tridonic software http www tridonic com com en software asp _ Download masterCONFIGURATOR http www tridonic com com en software masterconfigurator asp _ DALI manual http www tridonic com com en download technical DALI manual_en pdf _ Gu...