background image

                                      

 

 

 

 

2R2500 & 2R3500 Actuators 

 

 

 

 

 

 

 

 

 

Installation & Maintenance Manual 

  

 

November 13, 2013

www.atcontrols.com 

Engineering\documents\products/IOM\

IOM1004.docx

 

2R-SERIES 2R2500 & 2R3500 DOUBLE ACTING & SPRING RETURN 

SCOTCH YOKE ACTUATORS 

 

BRIEF INTRODUCTION 

 

TRIAC 2R2500 & 2R3500 scotch yoke actuators 

have been designed and engineered to provide high cycle-life 
to meet the demands of our customers.  Equipped with dual 
travel stops and NAMUR accessory mounting.   

 

!!!WARNING!!! 

 
FOR YOUR SAFETY, 

IT IS IMPORTANT THAT THE 

FOLLOWING PRECAUTIONS BE TAKEN BEFORE ANY 
DISASSEMBLY OF THE ACTUATOR OCCURS.   

1.

 

Depressurize the lines and cylinder of the actuator 
before removing any components. 

2.

 

On spring return actuators be careful to loosen the 
end cap bolts evenly due to the preload on the 
springs.   

 
 

Installation of Actuator

 

Triac actuators are adapted to the valve by means of an 
intermediate bracket and coupler.  The coupler adapts the star 
output of the actuator to the valve shaft.  Standard mounting 
kits provided for mounting the actuator in the direction of the 
pipe. 
After mounting the actuator, it may be necessary to adjust the 
travel stops for proper open or closed valve position.  
Pneumatically stroke the actuator several times to assure 
proper operation with no binding of the coupler.  
 

Air Supply

 

Pneumatic piping to the actuator and associated accessories 
should follow the best practices for instrument pneumatic 
piping systems, I.E. lines free of water, oil, pipe sealant or 
other contaminants.  The operating medium is to be filtered 
dry air or inert gas which is filtered to 50 micron particles size 
or less.  It is extremely important that the actuator be powered 
with the proper air pressure and air volume.  Maximum 
working pressure is 150 PSI. 
The spring housing on spring return actuators, if not piped, 
will breathe through the right hand port.  It’s important that it 
not be exposed to a corrosive atmosphere.  Please contact A-T 
Controls for possible solutions if this condition exists. 
 

Lubrication

 

Triac actuators are factory lubricated for life and additional 
lubrication is not normally required.  However, for actuators 
performing 100,000 cycles or more, an oil mist lubricator is 

recommended.  Oil mist lubrication requires a mineral oil type 
ISO VG32 Class 1 for usage in temperature range 15 to 158 
Deg. F.  Oil mist lubricator must be set to the lowest setting.  
Once begun, the oil mist lubrication cannot be discontinued. 

CAUTION 

If the actuator is equipped with a pneumatic positioner or 
pneumatic controller, oil mist lubricated air cannot be used 
unless the instrument manufacturer indicates that the 
instrument is compatible with lubricated air. 

 

Orientation of Pistons

 

Double Acting (DA)

 

The pistons of standard DA actuators are as shown below. 
This provides for the highest torque at the “closed” valve 
position for valves that rotate clockwise to close.  The pistons 
are then in their innermost position and the end of travel stop 
can be fine ad or – 5 degrees (SEE INSTRUCTIONS 
on page 2). 

 

(DL/SAH) 

Spring Return (SR) 

The pistons of standard SR actuators are mounted as shown 
below.  Although spring force is diminished, the geometry of 
the mechanism provides a greater torque at the end of the 
spring stroke than at mid stroke.  When the actuator is in the 
“opened” valve position (springs fully compressed), the end of 
travel stop can be fine ad or – 5 degrees (SEE 
INSTRUCTIONS on page 2). 

 

(SAH) 

 

 

Reviews: