14 Stove
Installation
(for qualified installers only)
© Travis Industries
100-01282
4150526
Mobile Home Requirements
Outside air must be installed - see "Outside Air Requirements" on page 12
Chimney connector and chimney must be one of the following types:
AMERI-TEC model DCC with model HS chimney
DURAVENT model DVL with DURATEC or DURA-PLUS chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
METALFAB model DW connector with TG chimney
OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
SELKIRK METALBESTOS model DS connector with model SSII chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE:
Reduced clearance connectors may not connect to the flue collar – an appliance adapter
may be required.
Stove placement must maintain the following clearances to combustibles (drywall, furniture, etc.)
Figure 8
Minimum Clearance
(See the illustration above)
Reduced Clearance
Connector
A
Sidewall to stove
12 ¾” (324mm)
B
Back wall to stove
11 ¾” (299mm)
C
Corner wall to stove
7 ¼” (185mm)
D
Connector to sidewall
26” (661mm)
E
Connector to back wall
12” (305mm)
F
Connector to corner wall
17” (432mm)
If using offsets, use the connector clearance listed in
Figure 9,
not the connector manufacturer's
clearance
.
The appliance must be secured to the floor (consult
your building official). Leg clips are available from
Travis Industries (sku 98900509).
Mobile
home
installations
require a spark arrester at
the chimney termination. Follow the chimney
manufacturer’s instructions for maintaining a proper
moisture barrier at the external chimney penetration.
The appliance must be grounded to the chassis of the
mobile home (consult your building official).
WARNING: DO NOT INSTALL IN SLEEPING ROOM.
CAUTION: THE STRUCTURAL INTEGRITY OF THE
MOBILE HOME FLOOR, WALL, AND CEILING/ROOF
MUST BE MAINTAINED.
Figure 9
A
B
F
C
Measure clearances from the
nearest edge of the stove top.
D
E
C
12” Min.
Connector Clearance
(as outlined above)
Stove Clearance
(as outlined above)