Travis Industries 564 HO GSR2 Installation Manual Download Page 13

 

Installation

 (

for qualified installers only)

 

13 

© Travis Industries 

4141013 

100-01414

 

Gas Line Requirements 

MASSACHUSETTS INSTALLATIONS -  WARNING: 

THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE 
COMMONWEALTH OF MASSACHUSETTS. 

OTHER MASSACHUSETTS CODE REQUIREMENTS: 

 

Flexible connector must not be longer than 36 inches. 

 

Shutoff valve must be a “T” handle gas cock. 

 

Only direct vent sealed combustion products are approved for bedrooms or bathrooms. 

 

Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log. 

 

A carbon monoxide (CO) detector is required in the same room as the appliance. 

 

The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and 
NFPA 54(88), in Canada follow CSA B149.1 and the requirements listed below. 

 

The fireplace and gas control valve must be disconnected from the gas supply piping during any 
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPA).  For pressures under 
1/2 psig (kPA), isolate the gas supply piping by closing the manual shutoff valve. 

 

Leak test all gas line joints and the gas control valve prior to and after starting the fireplace. 

Fuel 

 

This fireplace is designed either for natural gas or for propane (but not for both).  Check the sticker on the top of 
the gas control valve to make sure the correct fuel is used. 

Gas Line Connection 

 

Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a 
licensed plumber/gasfitter). 

Gas Inlet Pressure 

 

Standard Input Pressure 

 

Natural Gas 

1.74 kPa (Min. 1.13 kPa) 

 

Propane 2.74 

kPA 

 

If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately 
adjusted, and the total gas load for the residence does not exceed the amount supplied.   

 

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should 
supply gas at the suggested input pressure listed above.  Contact the local gas supplier if the regulator is at an 
improper pressure. 

Summary of Contents for 564 HO GSR2

Page 1: ...not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call gas supplier from a neighbor s phone Follow the gas supplier s instructions If...

Page 2: ...stment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual provided with this appliance For assistance or additional information consult a qua...

Page 3: ...tions with Horizontal Termination EmberFyre Burner only 21 Vent Configurations with Vertical Termination EmberFyre Burner only 22 Vent Configurations with Horizontal Termination Dancing DiamondFyre 23...

Page 4: ...t gases must be vented outside the structure of the living area Combustion air is drawn from outside the living area structure The venting must not be connected to a chimney flue serving a separate so...

Page 5: ...is provided with this appliance and shall be installed for the protection of children and other at risk individuals If the barrier becomes damaged the barrier shall be replaced with the manufacturer...

Page 6: ...ting Capacity in square meters Up to 158 Up to 158 Maximum MJ Input Per Hour 36 9 36 9 Heating capacity will vary with floor plan insulation and outside temperature Dimensions 36 25 921mm Weight 165 L...

Page 7: ...ble below to verify you have all of the items required Burner Style EmberFyre Burner 96900116 DiamondFyre Burner 96900115 DancingFyre Burner 96900114 Firebacks Requires 564 Ceramic Firebacks 96100179...

Page 8: ...ng Install the vent gas line and electrical hook up Install the drywall Install the hearth if applicable Install the facing if applicable Install the mantel if applicable Finalize the installation see...

Page 9: ...arpet This heater may be placed in a bedroom Please be aware of the large amount of heat this appliance produces when determining a location Clearances When installed walls in front of the fireplace m...

Page 10: ...10 Installation for qualified installers only 10 Travis Industries 4141013 100 01414 Minimum Framing Dimensions a Minimum Enclosure Height 36 5 928mm 36 75 936mm 17 75 451mm 56 1423mm a...

Page 11: ...tab out 90 use a screwdriver if necessary Fireplace Drywall Framing Nailing Bracket TOP VIEW 1 2 13mm Drywall 5 8 16mm Drywall There are four nailing brackets on the front of the fireplace Follow the...

Page 12: ...only 12 Travis Industries 4141013 100 01414 Corner Installations A typical 45 installation uses the framing dimensions shown in the illustration below NOTE all clearances still apply 14 1 4 362mm Mini...

Page 13: ...y pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPA For pressures under 1 2 psig kPA isolate the gas supply piping by closing the manual shutoff valve Leak test all gas l...

Page 14: ...fireplace on the right side 2 Remove the screw that holds the shutoff valve plate in place 1 4 nutdriver Remove the shutoff valve plate 3 Remove the cover plate from the left side of the fireplace it...

Page 15: ...er is shut off prior to working on any electrical lines The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Ele...

Page 16: ...must maintain the required clearance to combustible materials to prevent a fire Do not fill air spaces with insulation Sides 1 25mm Above 4 102mm Below 1 25mm Altitude Considerations This heater has...

Page 17: ...tructions for Simpson Dura Vent may be found at www duravent com Other vents may be approved Vent Installation Slide the vent sections together and turn 1 4 turn until the sections lock in place Screw...

Page 18: ...the restrictor positions The charts for acceptable vent configurations detail the correct restrictor positions Exhaust Restrictor Adjustment The exhaust restrictor is shipped in position 1 If the rest...

Page 19: ...nstalling this component Make sure to adjust the intake restrictor to the position indicated on the vent configuration page To adjust the restrictor loosen the two screws securing the restrictor to th...

Page 20: ...the diffuser to position 2 as follows 1 The diffuser is located above the exhaust restrictor remove the restrictor if necessary 2 Remove the diffuser 3 Bend the round portion of the diffuser so it is...

Page 21: ...m 0 feet 5 feet 1 5m 10 feet 3m 15 feet 4 5m 20 max 6m 15 feet 4 5m 21 max 6 4m 21 max 6 4m Exhaust Restrictor 5 2 LP 4 NG Maximum Exhaust Restrictor 1 Intake Restrictor 1 Diffuser Position 1 CLOSED E...

Page 22: ...onsidered a vertical elbow Horizontal length max 24 is calculated by adding both lengths of horizontal run Horizontal Length H1 H2 5 feet 1 5m 0 feet 0 feet 5 feet 1 5m 0 feet 20 feet 6m 20 feet 6m 5...

Page 23: ...0 feet 5 feet 1 5m 10 feet 3m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 21 max 6 4m 21 max 6 4m Exhaust Restrictor 5 2 LP 4 NG Maximum Exhaust Restrictor 1 Intake Restrictor 1 Diffuser Position...

Page 24: ...a 90 or 45 elbow This is considered a vertical elbow Horizontal length max 24 is calculated by adding both lengths of horizontal run Horizontal Length H1 H2 5 feet 1 5m 0 feet 0 feet 5 feet 1 5m 0 fe...

Page 25: ...es and the requirements of the gas supplier G Minimum 48 1219mm clearance from any adjacent building H Minimum 84 2134mm clearance above any grade when adjacent to public walkways or driveways NOTE ma...

Page 26: ...ring the fireplace must be raised so the base of the unit is above the carpet surface or flooring material Floor Mounted Fireplaces Raised Fireplaces WARNING A non combustible hearth is not required H...

Page 27: ...laced above the non combustible facing see b below and to the sides and below the fireplace face This combustible facing must be a minimum 3 77mm above the face of the fireplace see b below Tile or ot...

Page 28: ...28 Installation for qualified installers only 28 Travis Industries 4141013 100 01414...

Page 29: ...Installation for qualified installers only 29 Travis Industries 4141013 100 01414...

Page 30: ...is location 1 25mm above the base of the fireplace The fireplace may be raised to accommodate thicker hearth materials Optional Faceplates Sizing Chart Name Height Width Notes FPX Artisan Classic Fr C...

Page 31: ...convection air 27 3 4 705mm 1 1 7 8 48mm 32 1 2 826mm 1 1 2 38mm Tile 7 1 2 191mm 1 5 8 41mm Attach the facing to this edge of the fireplace Tile Line Tile Line Hearth Line Tile Line Floor mounted fir...

Page 32: ...ce Note how the facing extends 1 25mm above the base of the fireplace 1 25mm Fireplace Support Floor Tile or other facing under 1 25mm thick Face Floor Max 1 25mm Hearth note how it extends under the...

Page 33: ...y Raised Fireplaces Masonry is installed 1 25mm maximum above the base of the fireplace Floor Mounted Fireplaces or Raised Hearths Build the hearth 1 maximum 25mm above the base of the fireplace The f...

Page 34: ...pper corners FRONT VIEW TOP VIEW 61 Radius 1549mm 2 3 4 70mm 29 737mm 36 1 4 921mm Masonry Line Hearth Line The Fireplace Xtrodinair 564 Masonry Template is recommended for masonry installation sku 98...

Page 35: ...e masonry extends 1 25mm above the base of the fireplace 1 25mm Fireplace Support Floor Floor Mounted Fireplace with Hearth SIDE OF FIREPLACE Masonry or other non combustible over 1 25mm thick Face Fl...

Page 36: ...he side of the glass frame 0 from side of fireplace Combustible mantel columns legs that protrude between 19mm and 4 102mm from the glass frame or non combustible facing require a 5 127mm clearance to...

Page 37: ...bulbs are in place NOTE Take care to not touch the bulbs with your fingers use a cloth or paper towel 4 Install the four AA batteries see illustration below The AA batteries act as a power backup in c...

Page 38: ...his heater For comprehensive operating and maintenance instructions refer to the Owner s Manual ACID WASH WARNING Before installing the faceplate make sure any masonry that has been treated with acid...

Page 39: ...urer s barrier for this appliance If using a face or grill that requires use of a cove cover use the cove cover included with the fireplace see below Do not use the cover included with face or grill i...

Page 40: ...nstructions included with the face for details Open the 4 latches holding the glass frame in place starting with the bottom Follow the instructions shown to the right Latch Glass Top of Firebox Lift t...

Page 41: ...rn when it is disengaged Follow the directions below to re install the latch if it becomes loose Top of Firebox Hold the latch at an angle and insert it into the slot on the glass frame anchor NOTE th...

Page 42: ...lt causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installation of this kit The installation is not proper and complete until the ope...

Page 43: ...Replace the orifices as shown below Orifice Front Rear NG 50 44 LP 1 1mm 55 3 Install the LP burner bracket and manifold seal plate as shown below These components are shipped with the fireplace Front...

Page 44: ...the Natural Gas NG orifice Place the LP orifice in the pilot assembly then replace the pilot hood tightening the pilot hood until it is snug do not over tighten 5 Remove the concealment cover Unscrew...

Page 45: ...ation sheet included with it make sure to follow all of the directions Place the stepper motor on the gas control valve MAKE SURE IT IS CORRECTLY ORIENTED Secure using the screws included with the mot...

Page 46: ...n 13 Gas Line Location 13 Gas Line Requirements 13 Hearth Requirements 26 Heating Specifications 6 Installation Options 6 Intake Restrictor Adjustment 19 Error Reference source not found 2 Mantel Requ...

Reviews: