DIN  rail  mounted  DC  surge  protection  device,  designed  with  MOV 
technology to meet Type 2 requirements. Equipped with suppression status 
visual  indication  and  electrically  isol

ated  ‘Form  C’  dry  contacts  to  allow 

remote monitoring.  
 
 
 

 

 

 

 
 
 
Main Technical Data 
 

Electrical Performance 

 

Number Of Ports 

Single port device 

Technology 

MOV 

Nominal Operating Voltage U

n

 

1000 Vdc 

Maximum Continuous Operating Voltage U

c

 

1350 Vdc 

Nominal Discharge Surge Current I

n

 (8x20µs) 

20 Ka 

Maximum Discharge Surge Current I

max

 (8x20µs) Type 2 

40 kA 

Voltage Protection Level U

p

  

5 kV 

Response Time 

< 25 ns 

Recommended Over-Current Protection Device 

32A circuit breaker with C tripping characteristic (per IEC 60364-4-43) 

Status Indication 

Visual indication LED: Black = normal, Red = replace 
Contact switch for remote annunciation 

Maximum Contact Switch Rating 

250 Vac / 3 A 

 

 

Mechanical 

 

Location Category  

Indoor only 

Method of Mounting 

Fixed 35mm DIN rail 

Dimension (H x W x D) 

90mm x 54mm x 68

mm (3.6” x 2.2” x 2.7”) 

Weight (Max) 

0.33kg (0.74lb) 

Maximum Wire Size 

25 mm

(#4 AWG) 

Stripping Length Terminals 

10mm (0.375”) 

Torque Terminals 

4.5 Nm (3.3ft-lb) 

Maximum Wire Size Contacts 

1.5mm

2

 (#16AWG) 

Stripping Length Contacts 

7mm (0.25”) 

Torque Contacts 

1Nm (0.75ft-lb) 

 

 

Environmental

 

 

Operating Temperature 

-40ºC to +70ºC 

Relative Humidity 

≤95% non condensing 

Enclosure Protection Level 

IP20 

Housing Inflammability Rating 

PA66; UL94 V-0 

Certifications 

RoHS compliant 

 
 
 
 
 
 
 
 