Transition Networks, Inc.
PCVT-48VDC-53VDC Install Guide
33568 Rev. A
Page 13 of 18
Grounding Procedure
To properly ground the PCVT-48VDC-53VDC:
1. Obtain one (1) grounding conductor (12 AWG copper wire gauge or larger) with a two-hole,
compression-type, grounding connector.
2. Attach the grounding conductor to the PCVT-48VDC-53VDC by placing the two-hole connector onto
the grounding lugs and fasten with the enclosed lock-washers / lug-nuts at the proper torque (per the
manufacturer’s specification at the
) (4-5 inch-pounds typical
or “recommended”).
3. Attach the opposite end of the grounding conductor to the common bonding network (CBN) for
telecom, or to earth ground (if required) for non-telecom installations.
Figure 7: Grounding Conductor