INSTALLATION NOTES

Care must be taken when selecting the mounting location 

of sensor. The ambient light level may vary greatly at 

different measure points in the room, depending on the 

location of the windows, lighting fixtures, wall colors, floor 

material, desk top, etc.   
Note the path of shadows which may affect the sensor 

operation. Daylighting control may be problematic if part 

of controlled area is in shadows while other part has 

plentiful daylight.  
The sensor is designed to measure ambient light level by 

looking down from ceiling height. Sensing performance 

will vary if sensor is mounted to look out from wall. Avoid 

installing the sensor to directly look into the skylight, the 

daylight level could easily exceed the maximum threshold 

of sensor.         
The ambient light level on the ceiling can be much lower 

than that at the windows, corners of the room, or 

especially the workplace level. Therefore, it is important to 

set the optimum SmartDIM range based on the lighting 

level measured over the workplace.
Avoid placing the sensor at position that will receive strong 

light directly, such as within the lighting range of a 

pendent light with upward lamp.

1.

2.

3.

4.

5.

The BPD-502 series member of the TRANS family is a low 

voltage daylight sensor designed for automatic daylighting 

control. This sensor is capable of maintaining the ambient light 

level within a preset range via continuous dimming the 

connected lights based on the daylight available in the space. 

For the spaces with minor daylight, the sensor can also be used 

to provide energy efficient automatic dimming control, thus 

prevents energy waste from over lighting.  
This daylight sensor employs a cutting edge digital ambient light 

sensor (ALS) with an advanced SmartDIM control algorithm 

developed by IR-TEC to provide a closed loop, continuous 

dimming lighting control for achieving the energy efficiency 

required by today’s sustainable buildings. When daylighting 

level increases/decreases, the sensor will fade down/ramp up 

the connected lights in a smooth way to maintain the combined 

ambient light level within the preset range. The sensor will open 

its isolated dry contact to shut off the lights if ambient light level 

exceeds the shut-off threshold to maximize energy saving.       

            

Like all sensors in the TRANS family, the BPD-502 series is also 

available in various mounting options. This feature offers a 

second-to-none design and installation flexibility for daylight 

harvesting and control applications in sustainable buildings.   

The BPD-502 series daylight sensor can be applied to 
control the lights of areas that receive sufficient daylight, 
thus the electric lights can be reduced or switched OFF 
based on the daylight available in the space. Ensure that 
the sensor will not receive strong light directly.  

If the primary daylight source is a window, the daylight 
sensor is typically mounted between the window and the 
first row of fixtures.

Side-lighting area

If the primary daylight source is a skylight, the daylight 
sensor should be mounted on the ceiling between the 
skylight and fixtures, looking down at the floor.

Top-lighting area

SELECTING A LOCATION

AVERTISSEMENT & PRUDENCE

BPD-502

Ceiling

Light Fixture

Window

80°

Peak

Sensitivity

Typical Daylit Zone, about 12’ (3.6m)

Coupez l'alimentation au disjoncteur avant d'installer Power 
Pack ou capteurs.

Ne pas installer ou couvrir une boîte de jonction ayant les classes 1 
et 3 ou circuits de puissance et d'éclairage.
Classe 2 Câblage de périphériques Seulement - Ne PAS reclasser et 
installer Classe 1, 3 ou alimentation et circuits d'éclairage.

Turn power OFF at circuit breaker before installing Power Pack 
or Sensors. 

Do Not Install To and/or Cover a Junction Box Having  Class 1, 3 or 
Power and Lighting Circuits
Class 2 Device Wiring Only – Do Not Reclassify and Install as Class 
1, 3 or Power and Lighting Wiring

WARNING & CAUTION

P/N: 058-50200-004

Printed in Taiwan

www.irtec.com

This product may be covered by one or more U.S. patents or patent applications.

Please visit www.irtec.com for more information.

INDOOR USE ONLY
Utilisation a L'interieur Uniquement

BPD-502

Light Fixture

Skylight

80°

Ceiling