background image

INSTALLER'S GUIDE

18-HH08D10-2

Page 3

Figure 9 (Page 10)

Variable speed furnace with two step or two compressor
heat pump outdoor unit. For restricted operation, add
TAYSTAT250A Outdoor Thermostat. USE ONLY WITH
SYSTEM CONTROLLER CHIP VER. 2.8 or LATER.

Figure 10 (Page 11)

Variable speed two circuit air handler, matched with two
single speed heat pump outdoor units.

Figure 11 (Page 12)

Variable speed air handler, matched with a single speed
cooling unit and hydronic heat coil.

Figures 16-19

Packaged Units

WIRING

Route the  wiring through the wiring bushings provided in
the bottom of the system controller enclosure. Connect the
control wiring to the appropriate terminals on the termi-
nal blocks (

TB1, TB2, TB3 TB4

) provided. The terminal

blocks may be removed from the printed circuit board to
facilitate wiring.  The System Controller should be grounded
to the air handler  or furnace using the screw terminal
provided in the upper left corner of the controller.

Wiring between the Zone Sensors and the System Control-
ler is shown in Figure 12.  A separate 4 wire (#18 AWG
min.) thermostat cable may be run from each sensor to the
System Controller (home runned) or they may be daisy
chained. In all cases all "

R

" terminals must be connected

to "

R

" on the System Controller. The same is true of

terminals "

B

", "

S1

" and "

S2

".

Wiring (ordinary thermostat wire #18 AWG minimum)
between the Zone Control Cards and damper motors (and
24 volt power supply) is shown in Figure 14. Note that the
24 volt power supply must be connected to terminals 

4

 and

5

 (#

5

 is common) on one Zone Control Card (on each

Expander Board). Be sure to leave sufficient extra length
on all wire connecting to the Zone Control Cards to permit
unplugging of the card so that wiring connections can be
made and the three dip switches can be set for the maxi-
mum percentage of total system airflow required by that
zone. See Figure 15.

DIP SWITCH SETTINGS:

Before attempting to run the system be sure that the
twelve dip switches (

DSW

) at the top of the System

Controller and the four dip switches on the right side
(

SW1

) are properly set. Settings for the dip switches are

shown on the hookup diagrams. The twelve dip switches at
the top of the controller 

(DSW)

 are set to match the type

of system to be controlled (heat pump versus heat/cool,
single stage versus two stage, etc.). Operating choices,

three cycles per hour versus five cycles per hour., etc., can
also be selected. The four switches on 

SW1

 must also be

properly set for the desired mode of control.

Expander Board dip switch settings.

 Figure 15,

indicates dip switch settings for the Expander Board.

Four sets of three dip switches (DS1 through DS4) are
set for each zone/bypass control card.
DS #1 determines whether or not that zone can call

(Vote) for the equipment to operate.

DS #2 determines whether that zone card controls a

zone or a bypass damper (only one per system)

DS #3 is for future use (set to "OFF").

NOTE:
If a second Expander Board is used, the six dip switches
(

DS5

) on the second board are all set to "OFF".

DIGITAL VERSUS ANALOG ZONE CONTROL

When a zoned system has a Communicating Comfort
Sensor (digital control) in each zone, terminal block 

TB5

(on the Expander Board) is not used.

A Master Scheduler, (ZUSTATALMS2) can be used as one
of the Zone Comfort Sensors, in addition to being the
Master Scheduler. The Master Scheduler can also be
located remote from all zones and be used as a Master
Scheduler or  as an override only.

If  the Remote Analog Comfort Sensor (ZZSENSAL011) is
selected, for any, (or all) zones, the ZUSTATALMS2
Master Scheduler must be applied, to serve as  an inter-
face for the Remote Analog Comfort Sensor.

Each  Remote Analog Temperature Sensor must be con-
nected to its proper zone address on terminal block 

TB5

on the Expander Board (zone #1, zone #2, etc.).

Note that terminal 1/5 on terminal block 

TB5

 (on Ex-

pander Board) is zone #1 if it is on the first Expander
Board and zone #5 if it is on the second Expander Board
(farthest right). The same is true of terminals 2/6, 3/7 and
4/8.

Here again the Master Scheduler will act as the overall
controller for all Remote Analog Comfort Sensors , and
(override) all Communicating Comfort Sensors (it can
also be used as a Communicating Comfort Sensor to
control a zone, if located in that zone).

Summary of Contents for ZSASSMAL012

Page 1: ... senses indoor conditions andcustomercommandsandtransmitsthisinformationto the System Controller All system electrical control func tions are provided by the System Controller GENERAL These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with installation This Installer s Guide covers multiple zone applications of the ZSASSMAL0...

Page 2: ...or unit in a single cabinet C Two separate cooling only outdoor units Dual fuel heat pumps not included see Figure 9 It is recommended that a separate 24 volt transformer be utilized to power the damper motors When selecting a transformer add up the V A consumption of all damper motors not watts and select a transformer rated at that V A value or higher preferably a fused transformer If the V A co...

Page 3: ... four dip switches on the right side SW1 are properly set Settings for the dip switches are shownonthehookupdiagrams Thetwelvedipswitchesat the top of the controller DSW are set to match the type of system to be controlled heat pump versus heat cool single stage versus two stage etc Operating choices three cycles per hour versus five cycles per hour etc can also be selected The four switches on SW...

Page 4: ...f 5 minutes and a normal minimum compressor run time of 3 minutes A test mode is available to bypass the time delay and operate the system at several speeds See the hook updiagramforyourparticularcombinationofequip ment for switch settings later in this guide NOTE If the test mode is used make certain the dip switches are returned to proper settings after testing is completed The test mode is ente...

Page 5: ...sor positionthesensorsothattheblackthermistor sensor faces away from the radiant heat source This will prevent a false reading due to the radiant effect on the thermistor see Figure 3 If no radiant heat source is in line of sight position the sensor with the sensing element facing into the air stream fastest response When the proper positioning has been determined mark the location of the four hol...

Page 6: ...perature of the air in the duct and record Connect an accurate ohmmeter across the two leads of the sensor and record the resistance value thus obtained Compare the values obtained temperature and resistance to the values indicated by the curve in Figure 6 A reading within 10 of the indicated value is acceptable DISCHARGE AIR SENSOR SYSTEM CONTROLLER TB4 T1 T2 T3 C CONNECTIONS AT SYSTEM CONTROLLER...

Page 7: ... W T W T W B M B M B M B M B M B M B M B M B M B M B M B M 5 7 2 1 7 1 1 6 0 1 6 0 1 6 9 5 8 6 1 1 1 8 1 0 1 6 1 9 5 1 8 4 1 8 3 1 7 2 1 7 1 5 1 4 2 1 3 1 2 2 1 2 1 0 2 1 1 1 9 1 1 1 1 8 1 0 1 7 1 8 1 2 9 1 2 3 2 8 1 9 2 2 6 1 7 2 2 5 1 5 2 1 4 1 3 2 1 3 1 2 2 0 1 2 4 0 3 9 4 1 3 7 2 5 4 1 3 5 2 2 4 1 3 3 2 9 3 1 2 2 2 6 3 1 2 0 2 4 3 2 1 3 5 3 4 2 7 3 5 9 3 6 6 2 4 6 3 1 6 2 4 4 3 6 5 2 4 1 3 3 5...

Page 8: ...D INDOOR UNIT FURNACE OR AIR HANDLER WITH SINGLE SPEED OUTDOOR UNIT COOLING OR HEAT PUMP INCLUDING DUAL FUEL HEAT PUMP NO PLUS ONE KIT REQUIRED DSW 2 OFF ONLY ON IF OTHER DIGITAL SENSORS ARE USED ONLY USE ON VER 2 8 or LATER OFF RES AIRFLOW ON COMML AIRFLOW OFF ONE TWO STAGE AIRFLOW ON TWO STEP SCROLL AIRFLOW DSW9 FOR MULTI STAGE COMPRESSORS OR TWO STAGE HEATING DSW10 DSW11 NOTE 8 MULTI STAGE COMP...

Page 9: ...UNIT B TWO COMPRESSOR COOLING OR HEAT PUMP OUTDOOR UNIT SW1 3 ON DSW 2 ON C TWO SEPARATE OUTDOOR UNITS COOLING ONLY DSW 2 ON NOTE DUAL FUEL HEAT PUMPS NOT INCLUDED SEE APPROPRIATE FIGURE STEP OFF ONE TWO STAGE AIRFLOW ON TWO STEP SCROLL AIRFLOW YL BK X2 MULTI STAGE COMPRESSORS 8 REMOVE BK JUMPER ON VS AIR HANDLERS OR CUT BK JUMPER ON VS FURNACE INTERFACE BOARD FOR MULTI STAGE COMPRESSORS OR TWO ST...

Page 10: ...ON ONLY ON IF OTHER DIGITAL SENSORS ARE USED ADD O D T FOR RESTRICTED MODE OPERATION TAYSTAT250A ONLY USE ON VER 2 8 or LATER OFF RES AIRFLOW ON COMML AIRFLOW DSW9 DSW10 DSW11 OFF ONE TWO STAGE AIRFLOW ON TWO STEP SCROLL AIRFLOW YL BK X2 MULTI STAGE COMPRESSORS 7 REMOVE BK JUMPER ON VS AIR HANDLERS OR CUT BK JUMPER ON VS FURNACE INTERFACE BOARD FOR MULTI STAGE COMPRESSORS OR TWO STAGE HEATING NOT ...

Page 11: ...1 1 2 2 2 1 2 OR 3 TON UNITS ONLY ON IF OTHER DIGITAL SENSORS ARE USED OFF RES AIRFLOW ON COMML AIRFLOW DSW9 DSW10 DSW11 MULTI STAGE COMPRESSORS 4 6 7 8 9 REMOVE BK JUMPER ON VS AIR HANDLERS OR CUT BK JUMPER ON VS FURNACE INTERFACE BOARD OFF ONE TWO STAGE AIRFLOW ON TWO STEP SCROLL AIRFLOW FOR MULTI STAGE COMPRESSORS OR TWO STAGE HEATING NOT WITH ZUSTAT031 Figure 10 ...

Page 12: ...R VARIABLE SPEED INDOOR UNIT WITH SINGLE SPEED COOLING OUTDOOR UNIT ONLY ON IF OTHER DIGITAL SENSORS ARE USED RELAY BAY24X042 FOR PUMP NEAR AIR HANDLER AIR HANDLER 3 NOTE 4 NOTE 3 DSW9 DSW10 DSW11 MULTI STAGE COMPRESSORS FOR MULTI STAGE COMPRESSORS OR TWO STAGE HEATING HYDRONIC HEAT COIL NOT WITH ZUSTAT031 Figure 11 ...

Page 13: ...ENSORS IN ZONED SYSTEMS SEE NOTE 1 REMOTE ANALOG SENSOR ZZSENSAL011 OPTIONAL ZUSTATALMS2 MASTER SCHEDULER TB1 Figure 12 ZONE BYPASS CONTROL CARD SWITCH SETTINGS OFF ON TB1 DSW OPEN CLOSE DUMP 1 2 3 1 2 3 24V COM DUMP IF APPLICABLE CLOSE OPEN 24 VAC R COM B ZONE BYPASSCONTROLCARD ZZCARDAL0100 USE DIP SWITCH TO SET MAXIMUM PERCENT OF EQUIP MENT CFM TO BE SUPPLIED TO EACH INDIVIDUAL ZONE ZONE DAMPER ...

Page 14: ...0 ZONE EXPANDER BOARD ZZEXPDAL010 ZONE EXPANDER BOARD ZZEXPDAL010 ZONES 1 4 PLUG IN ZONE BYPASS CONTROL CARDS ZZCARDAL010 ANALOG SENSOR ZZSENSAL011 NOTE 7 TO DUMP DAMPER MOTER IF USED TB5 THERMOSTAT ZUSTATAL031 ZUSTATALS51 ZUSTATALP51 OR ZUSTATALMS1 WHEN TWO 2 ZONE EXPANDER BOARDS ARE INSTALLED JUMPER 24 VOLT POWER FROM TERMINALS 4 24V 5 COM ON THE FIRST ZONE CARD TO TERMINALS 4 24V 5 COM ON THE F...

Page 15: ...DARD ON WARM AIR CFM V S BLOWER ONLY W HEAT PUMP 3 OFF 3 CYCLE ON 5 CYCLE COOLING 4 OFF NORMAL ON TEST MODE 1 OFF SYSTEM FAN CONT ON Z0NE FAN CONT 2 OFF STANDARD BLOWER MOTOR ON VARIABLE SPEED BLOWER 3 OFF NO RELIEF ON RELIEF AIR CONTROL STRATEGY 6 OFF STD DISCHARGE AIR TEMP SETPOINT ON EXTENDED RANGE NOTE IF SECOND EXPANDER BOARD IS USED SET ALL SIX SWITCHES ON SECOND BOARD TO OFF POSITION 2 OFF ...

Page 16: ...USE ON VER 2 8 or LATER OFF RES AIRFLOW ON COMML AIRFLOW DSW9 DSW10 DSW11 OFF ONE TWO STAGE AIRFLOW ON TWO STEP SCROLL AIRFLOW YL MULTI STAGE COMPRESSORS W1 W2 Y1 Y2 O R G B 35A 47A 41A 41B 41C 36B 41D 53A 81A 39A 4YCZ6 4DCZ6 4WCZ6 4DCZ6 4WCZ6 67A 4WCZ6 4DCZ6 4YCZ6 73A 4WCZ6 4DCZ6 ICMC BK REMOVE JUMPER 91A BK W SEPARATE AT CN 10 REMOVE FROM W1 39A DFC X2 65B 81B ICMC REMOVE CAP OFF IGN X2 FIELD SU...

Page 17: ...INSTALLER S GUIDE 18 HH08D10 2 Page 17 4DCZ6 PACKAGED UNIT Figure 17 CAP CAP REMOVE REDIRECT 41D TO D ON TB3 CUT FIELD SUPPLIED WIRE TO BK ON TB2 ...

Page 18: ...INSTALLER S GUIDE 18 HH08D10 2 Page 18 4WCZ6 PACKAGED UNIT Figure 18 CAP REDIRECT 41C TO W2 ON TB2 REDIRECT 41D TO D ON TB3 TO BK ON TB2 REMOVE CAP CAP FIELD SUPPLIED WIRE ...

Page 19: ...INSTALLER S GUIDE 18 HH08D10 2 Page 19 4YCZ6 PACKAGED UNIT Figure 19 TO BK ON TB2 REMOVE CAP CAP FIELD SUPPLIED WIRE ...

Page 20: ...icy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200TroupHighway Tyler TX75711 For more information contact your local dealer distributor INSTALLER SGUIDE ...

Reviews: