SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation,
starting up, and servicing of heating, ventilating, and air-conditioning equipment can
be hazardous and requires specific knowledge and training. Improperly installed,
adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
© 2020 Trane
2
1
3
4
5
Installation Instructions
Air-Fi® Wireless
Communications Interface (WCI)
Model Number:
X13790901030, X13790902030, X13790903030,
X13790904030, X13790941030
Set Addresses
WCI
WCI
GRP NET
GRP NET
GRP NET
2
1
2
1
2
1
WCI
WCI
WCI
GRP NET
GRP NET
GRP NET
2
2
2
2
2
2
WCI
SC - 2
Device
Device
Device
Device
SC - 1
GRP NET
1
1
WCI
GRP NET
1
2
WCI
Device
Device
WCI
WCI
GRP NET
NET
1
1
1
WCI
WCI
GRP NET
GRP NET
1
2
1
2
Device
Device
GRP
1
1
2 3 4
5
6
78
9
0
NET
GRP
1
2 3 4
5
6
78
9
0
For detailed information and procedures, refer to the
following documents:
• Air-Fi
®
Wireless Installation, Operation, and
Maintenance
(BAS-SVX40*)
•
Air-Fi
®
Wireless Network Design Best Practices
Guide
(BAS-SVX55*)
June 2020
BAS-SVN038C-EN
Connecting the Wiring Harness to the WCI
Gray = LINK–
Blue = LINK+
Red = +24VDC/VAC
Black =
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death or serious
injury.
CAUTION
Indicates a potentially hazardous situation which,
if not avoided, could result in minor or moderate
injury. It could also be used to alert against unsafe
NOTICE
Indicates a situation that could result in
equipment or property-damage only accidents.
X39641361001
WCI
MSTP
VAC
24
BI
1
BI
2
BI
3
LINK
IMC
+
24
VDC
IMC
Jumper
LINK -
LINK +
+24 Vdc
WCI
BCI-I
+24 VDC/VAC
Use a PM014 with Tracer SC with 1 or more
wireless networks, or Tracer SC+ when needed
to stay within IMC power budget.
PM014
WCI wiring
LINK +
LINK –
+ 24VDC
IMC– IMC+
Ground 24
Vdc
Power OFF
Device
+
24
VDC
IMC
LINK
IMC
LINK+
LINK–
+24 Vdc
WCI
UC
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure that power cannot be
inadvertently energized. Failure to disconnect power before servicing could
result in death or serious injury.
Tracer SC/SC+
UC 210/400/600
BCI-I (IntelliPak/CSC)
BCI-R (ReliaTel™: Voyager™, Precedent™, and Odyssey™)
WCI as Repeater
Connect WCI Wires to Controller
Note:
It is normal for the
Repeater DIAG LED to flash.
Note:
Field-supplied.
Connect both 2-connector screw
terminal blocks to either of the
IMC terminals on the PM014.
Power ON Device
Note:
If all devices
cannot be powered on at
the same time, the best
practice is to power them
on in the following order:
1. All WCIs
2. All unit controllers:
UC210, UC400,
UC600, BCI-I, BCI-R
3. All Tracer SCs
4. All WCSs
Tracer SC+
WCI Wiring
Tracer SC+ when IMC power budget allows