UH-SVX01A-EN
17
Installation
Notes:
To meet OSHA requirements, units mounted lower than 8 feet from the floor must be equipped with an OSHA fan guard.
Figure 15.
Table 7.
Mounting Height Correction Factors
Water
°F
150
160
170
180
190
200
Temperature
(°C)
(66)
(71)
(77)
(82)
(88)
(93)
Steam
PSI
-
-
-
-
-
-
Pressure
(kPa)
-
-
-
-
-
-
Correction Factor
1.32
1.27
1.23
1.18
1.14
1.09
Water
°F
210
219
227
239
250
259
Temperature
(°C)
(99)
(104)
(108)
(115)
(121)
(126)
Steam
PSI
-
2
5
10
15
20
Pressure
(kPa)
-
(13.8)
(34.5)
(68.9) (103.4) (137.9)
Correction Factor
1.05
1.00
0.97
0.94
0.89
0.86
Water
°F
267
280
287
298
307
320
Temperature
(°C)
(131)
(138)
(142)
(148)
(153)
(160)
Steam
PSI
25
35
40
50
60
75
Pressure
(kPa)
(172.4) (241.3) (275.8) (344.7) (413.6) (517.1)
Correction Factor
0.83
0.80
0.76
0.73
0.70
0.69