background image

8

MS-SVN005-EN

Connection of Refrigerant Tubing

Table 4

 Tube Diameter Tightening

Torque

mm.

in.

kg - cm

lbs - in.

6.35

(1/4)

150 - 200 (130 - 170)

9.52

(3/8)

350 - 400 (300 - 340)

12.70

(1/2)

500 - 550 (430 - 470)

15.88

(5/8)

600 - 650 (520 - 570)

1. The principal concerns in

refrigeration tubing are:

- Uniform oil return to the

compressor.

- Pressure drops and their effect on

system capacity.

- Tube routing and isolation to avoid

line breakage, vibration and sound
transmission. Regarding this, the
interconnecting refrigerant lines
should be simple and shorter as
much as possible.

2. Flare Connections
The units reported in this manual
employ the flare method to
interconnect refrigerant tubes between
indoor and outdoor units (Figure 2).
- The tube end of all refrigerant tubes

should be flared, the tube should
be cut and deburred. Be sure no
copper scraps fall in to the tube.

- Be sure to fit a cap to the open end

of the tube to keep it free of dust
and moisture.

- Avoid bending the tube. If it is

necessary, bend it gently, with a
radius of more than 3 or 4 cm.
(1 1/2 in. or 1 5/8 in.)

- Cut approximately 30 to 50 cm.

(12 in. to 20 in.) longer than
estimated tubing length.

- Before flaring remember to fit

the nut.

- Ream with tube end downward

to avoid copper scraps inside
the tube.

- Remove the flare caps on the

tube end.

- Connect the tubes by aligning

the centers of both flares and turn
the flare nuts by hand 3 or 4 turns
(Figure 3).

3. Insulate both lines, liquid (narrow
tube) and suction (wide tube), to
prevent heat loss and wet floor due to
dripping of chilled condensation.
Apply proper insulation material,
minimum thickness should be 8 mm
(1/3 in.) (Figure 4).

Note

Do not try to bend the tube after
installation.

4. Finish with armoring tape.
Also see section of condensate drain
piping.

Note

Apply refrigeration oil on flare and
union surfaces before connecting
them. This will reduce refrigerant
leakage.

- Check the tubing connections and

refrigerant lines before applying
specified torque. Fasten flare nuts
as recommended below.

Figure 4

Figure 3

Figure 2

Electrical Connection

Service Port

Valve Cap

Tube
Connection
(Flare)

Liquid Line System # 1

Gas Line System # 1

Liquid Line System # 2

Gas Line System # 2

Liquid Line System # 3

Gas Line System # 3

Union

Flare nut

,,

,,

,,

yy

yy

yy

,,,

,,,

yyy

yyy

Insulation Thickness

Min. 8 mm

Min. 8 mm (1/3 in.)

Summary of Contents for TTD 518 A10E

Page 1: ...D 524 A10E TTD 524 A100 TTT 527 A10E TTT 530 A10E TTT 533 A10E 50 Hz Models Cooling Only TTD 518 AB0E TTD 521 AB0E TTD 524 AB0E TTD 524 AB00 TTT 521 AB0E TTT 527 AB0E TTT 530 AB0E TTT 533 AB0E TTD 536...

Page 2: ...days of delivery and notify the dealer Warning Warnings are provided at appropriate places in this manual to indicate to installers operators and service personnel of potentially hazardous situations...

Page 3: ...lid System Combinations 4 Installation Requirements 6 Location and Preparation of Units 7 Connection of Refrigerant Tubing 8 Condensate Drain Piping 9 System Evacuation and Purging 10 Electrical Insta...

Page 4: ...9 000 MCW509H 9 000 MCW509H 9 000 Yes Yes TTT530AB0E A10E MCW509H 9 000 MCW512H 12 000 MCW509H 9 000 Yes Yes TTT533AB0E A10E MCW512H 12 000 MCW512H 12 000 MCW518H 18 000 Yes Yes MCW518H 18 000 MCX518...

Page 5: ...000 MCW509K 8 600 Yes Yes TTT527AB0E A10E MCW509K 8 600 MCW509K 8 600 MCW509K 8 600 Yes Yes TTT530AB0E A10E MCW509K 8 600 MCW512K 11 000 MCW509K 8 600 Yes Yes TTT533AB0E A10E MCW512K 11 000 MCW512K 11...

Page 6: ...r on each one to deepen vibration between units Wall thickness of copper tube should be 0 8 mm 0 0314 in Both tubes must be well insulated with proper insulation materials The length of wiring will de...

Page 7: ...concrete pad with bolts not supplied to prevent abnormal noise and vibration 5 The concrete pad must be positioned a minimum of 200 mm 8 from any well and surrounding shrubbery 6 Minimum clearance on...

Page 8: ...5 8 in Cut approximately 30 to 50 cm 12 in to 20 in longer than estimated tubing length Before flaring remember to fit the nut Ream with tube end downward to avoid copper scraps inside the tube Remov...

Page 9: ...hose in water 3 To avoid damage to the floor or furniture when the drain hose is placed in the room insulate the hose with foamed polyethylene or equivalent 4 After completing refrigerant lines winin...

Page 10: ...00 microns in one 1 minute then evacuation is incompleted or system is leaking Attach appropriate hose from manifold gauge to suction and liquid line valves service ports Attached center hose of mainf...

Page 11: ...d size Note Each country has their own field wiring rules and regulations Be sure the installation complies with local electrical codes Nameplate ratings on indoor units are for one to one system inst...

Page 12: ...12 MS SVN005 EN Wiring Diagram 220 240 1 50 Hz 200 240 1 60 Hz...

Page 13: ...MS SVN005 EN 13 220 240 1 50 Hz 200 240 1 60 Hz...

Page 14: ...14 MS SVN005 EN...

Page 15: ...MS SVN005 EN 15...

Page 16: ...16 MS SVN005 EN...

Page 17: ...MS SVN005 EN 17 Dimensional Data Models 50Hz TTT521AB0EA...

Page 18: ...527AB0EA TTT527A10EA TTT530AB0EA TTT530A10EA TTT533AB0EA TTT533A10EA TTD536AB0EA TTD536A10EA TTD536AB00A TTD536A100A TTT536AB0EA TTT536A10EA TTT536AB00A TTT536A100A TTD536DB00A TTD536D100A TTD536DB0EA...

Page 19: ...MS SVN005 EN 19 Models 50Hz 60Hz TTD518AB0EA TTD518A10EA TTD521AB0EA TTD521A10EA TTD524AB0EA TTD524A10EA TTD524AB00A TTD524A100A...

Page 20: ...ions without notice Literature Order Number MS SVN005 EN 0601 Supersedes MS SVN005 EN 0300 Stocking Location Bangkok Thailand Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongt...

Reviews: