Trane TTA240F Series Application Manual Download Page 18

12

 SS-APG008-EN

Remodel, Retrofit, or Replacement

Inevitably, older condensing unit/evaporator systems that are designed for use with a refrigerant 
other than R-410A will need to be upgraded. Due to the phase-out of many of these older 
refrigerants, the major components for those older condensing unit/evaporator systems may no 
longer be available. The only option will be to convert the system to R-410A, POE oil, and R-410A 
components.

When upgrading an existing refrigerant split system due to remodel, retrofit, or replacement, the 
entire system must be reviewed for compatibility with R-410A and POE oil. Each and every part of 
the split HVAC system MUST be compatible with the properties of R-410A refrigerant and POE oil. 
In addition, ensure the existing electrical service and protection are correct for the product being 
installed.

WARNING

R-410A Refrigerant under Higher Pressure than R-22!

The units described in this manual use R-410A refrigerant, which operates at higher pressures 
than R-22 refrigerant. Use ONLY R-410A rated service equipment or components with this unit. 
For specific handling concerns with R-410A, please contact your local Trane representative. 

Failure to use R-410A rated service equipment or components could result in equipment or 
components exploding under R-410A high pressures which could result in death, serious injury, 
or equipment damage.

Every part of an existing split system needs to be analyzed to determine if it can be reused in an 
R-410A and POE oil system:

R-22 condensing units will not work with R-410A. 

Most older evaporator coils were not pressure and cycle rated for R-410A pressures. If they 
weren’t, they will need to be replaced. Check with the manufacturer.

Suction lines 2-5/8 OD and smaller of type L copper are suitable for use with R-410A. Suction 
lines 3-1/8 OD must use type K or thicker wall. 

Discharge lines, liquid lines, heat pump vapor lines, and hot gas bypass lines 1-3/8 OD and 
smaller of type L copper are suitable for use with R-410A. These same lines sized at 1-5/8 OD 
or 2-1/8 OD must use type K or thicker wall.

R-410A refrigerant line sizes may be different than the existing line sizes. The lines need to be 
re-sized and compared to existing lines for reusability.

Expansion valves need to be reselected. Expansion valves are refrigerant specific. 

Any gasket or o-ring should be replaced. Shrinkage of the original seal may occur after an HFC 
conversion, potentially causing a refrigerant leak. Components commonly affected are 
Schraeder cores, solenoid valves, ball valves, and flange seals. But 

all

 external seals in contact 

with refrigerant should be viewed as potential leak sources after a retrofit.

All other valves, filters, valve packing, pressure controls, and refrigeration accessories must be 
researched through their manufacturer for compatibility with the pressures of an R-410A 
system, and for their compatibility with the newer POE oil. 

For the best performance and operation, the original mineral oil should be removed from the 
components of the system that are not being replaced. Any component of the system that is 
suspected of trapping oil (piping, traps, and coil), should be dismantled, drained, and 
reassembled. After all components have been drained, the amount of residual mineral oil will 
have a negligible effect on performance and reliability.

Note: POE oil is hygroscopic—it absorbs water directly from the air. This water is nearly 

impossible to remove from the compressor oil and can cause compressor failures. For this 
reason, the system should not be open for longer than necessary, dry nitrogen should flow 
in the system while brazing, and only new containers of oil should be used for service and 
maintenance. 

All Codes take precedence over anything written here. 

Summary of Contents for TTA240F Series

Page 1: ...nd Component Selection for TTA and TWA Split Systems 6 20 Tons Using Refrigerant 410A Model Numbers TTA073D TTA090D TTA120D TTA120E TTA120F TTA150E TTA180E TTA180F TTA240E TTA240F TWA073D TWA120D TWA1...

Page 2: ......

Page 3: ...ent our customers and the air conditioning industry All technicians who handle refrigerants must be certified The Federal Clean Air Act Section 608 sets forth the requirements for handling reclaiming...

Page 4: ...e is a risk of arc or flash technicians MUST put on all necessary Personal Protective Equipment PPE in accordance with NFPA70E for arc flash protection PRIOR to servicing the unit Failure to follow re...

Page 5: ...f airflow and that provide no more than 45 percent ventilation outdoor air Prospective applications outside this operating envelope including low ambient process and 100 percent outdoor air applicatio...

Page 6: ...es 2 Equipment Placement 3 Line Sizing Routing and Component Selection 5 Liquid Lines 5 Line Sizing 5 Routing 5 Insulation 5 Components 5 Gas Line 7 Line Sizing 7 Routing 7 Insulation 8 Components 8 E...

Page 7: ...accumulated over years of observation demonstrates that the lower the refrigerant charge the more reliably a split air conditioning system performs Any amount of refrigerant in excess of the minimum...

Page 8: ...thin the piping circuit Oil movement through the piping wasn t a concern nor is it today because oil is miscible in liquid refrigerant at normal liquid line temperatures The historic and traditional 6...

Page 9: ...interconnecting refrigerant line by the shortest and most direct path so that line lengths and riser heights are no longer than absolutely necessary Use only horizontal and vertical piping configurati...

Page 10: ...iew Figure 2 Allowable elevation difference Cooling only TTA above indoor unit Figure 3 Allowable elevation difference TWA heat pump above indoor unit Figure 4 Allowable elevation difference TTA or TW...

Page 11: ...tion In fact heat loss from the liquid line improves system capacity because it provides additional subcooling If the liquid line is routed through a high temperature area such as an attic or mechanic...

Page 12: ...icating ability Use the Installation manual charging curves not the sightglass to determine proper charge levels Expansion Valve The expansion valve is the throttling device that meters the refrigeran...

Page 13: ...ard the indoor coil Do not install riser traps With field supplied air handler coils what appears to be a riser trap is located at the coil outlet see Figure 5 for an example This piping arrangement w...

Page 14: ...ngs and joints to verify that the system is leak free insulate the gas lines to prevent heat gain and unwanted condensation Components Adding a gas line filter is unnecessary provided that good refrig...

Page 15: ...ual distributors 10 2 5 Each TXV should be selected for 5 tons Example 2 10 ton coil one refrigerant circuit with two distributors and a 60 40 coil split 10 x 6 6 and 10 x 4 4 One TXV should be sized...

Page 16: ...r to the third party Simply stated this means that when a compressor turns on it shouldn t turn off until the expansion valve comes under control And once the compressor turns off it should be allowed...

Page 17: ...roblems Finally hot gas bypass uses excessive amounts of energy by preventing the compressors from cycling with fluctuating loads Trane now has several years of successful experience with Evaporator D...

Page 18: ...e for use with R 410A Suction lines 3 1 8 OD must use type K or thicker wall Discharge lines liquid lines heat pump vapor lines and hot gas bypass lines 1 3 8 OD and smaller of type L copper are suita...

Page 19: ...length of the liquid line exceeds 80 ft 24 m remove the liquid line filter drier from the TTA and install a new one Table 2 p 20 at the TWE air handler 1 If the total length of the liquid line exceeds...

Page 20: ...cal arrangement shown in cooling mode 1 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liquid line filter driers fr...

Page 21: ...s one thermal expansion valve TXV and one check valve See Table 3 and Table 4 p 21 for recommendations 2 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will...

Page 22: ...ble 3 p 21 2 Provide one expansion valve TXV per distributor TWA heat pumps only Provide one check valve for each expansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the...

Page 23: ...er 10 feet 1 cm per 3 m 4 Arrange the gas line so that suction gas leaving the coil flows downward past the lowest gas header outlet before turning upward Use a double elbow configuration on all lower...

Page 24: ...3 p 21 2 Provide one expansion valve TXV per distributor TWA heat pumps only Provide one check valve for each expansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil...

Page 25: ...nch per 10 feet 1 cm per 3 m 4 Arrange the gas line so that suction gas leaving the coil flows downward past the lowest gas header outlet before turning upward Use a double elbow configuration on all...

Page 26: ...eder valve w core LIQUID LINE LIQUID LINE Tube diameter in 1 2 5 8 1 2 1 2 1 2 1 2 1 2 5 8 1 2 5 8 Filter drier DHY01123 DHY01232 DHY01123 DHY01123 DHY01123 DHY01123 DHY01123 DHY01131 DHY01123 DHY0113...

Page 27: ...6 3 8 VAL08459 1 2 VAL08460 5 8 VAL01722 Valve body VAL01483 valve core COR00006 valve cap CAP00072 The heat pump products require two filters and two check valves one set oriented for liquid in the...

Page 28: ...r Number SS APG008 EN Date October 2009 Supersedes New Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice O...

Reviews: