21
SS-PRC003-EN
Performance
Data
System
Table PD-8 — Gross Cooling Capacities (MBh) - Single Compressor - TTA100C Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85
95
105
115
Enter.
Dry
Entering Wet Bulb (°F)
CFM
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
Airflow
(°F)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
75
63.8
62.6
69.8
46.0
76.2
29.7
61.3
61.3
67.2
45.0
73.4
28.6
59.2
59.2
64.6
43.8
70.4
27.7
57.0
57.0
61.8
42.6
67.1
26.6
3025
80
67.3
67.3
70.1
59.5
76.9
43.1
65.2
65.2
67.6
58.5
74.0
41.8
63.0
63.0
65.0
57.4
71.1
40.7
60.7
60.7
62.2
56.3
68.1
40.8
85
71.2
71.2
71.3
71.3
77.1
56.3
69.1
69.1
69.2
69.2
74.4
55.3
66.8
66.8
66.9
66.9
71.5
54.2
64.4
64.4
64.5
64.5
68.5
53.1
90
75.2
75.2
75.3
75.3
77.5
69.9
73.0
73.0
73.1
73.1
74.8
69.0
70.7
70.7
70.8
70.8
72.0
67.9
68.2
68.2
68.3
68.3
69.1
66.8
75
64.8
64.8
70.6
48.6
76.9
29.7
62.7
62.7
67.9
46.8
74.0
28.7
60.5
60.5
65.2
45.7
70.9
27.7
58.2
58.2
62.4
44.4
67.5
26.7
3350
80
68.8
68.8
70.9
62.7
77.7
44.9
66.7
66.7
68.4
61.6
74.8
44.0
64.4
64.4
65.7
60.5
71.9
43.0
62.0
62.0
63.0
59.4
68.7
42.0
85
72.9
72.9
73.0
73.0
77.9
59.1
70.7
70.7
70.8
70.8
75.1
58.1
68.4
68.4
68.4
68.4
72.2
57.0
65.9
65.9
65.9
65.9
69.1
55.9
90
77.0
77.0
77.1
77.1
78.4
74.0
74.7
74.7
74.8
74.8
75.7
73.0
72.3
72.3
72.4
72.4
73.0
72.0
69.7
69.7
69.8
69.8
69.8
69.8
75
66.0
66.0
71.2
49.7
77.4
30.2
63.9
63.9
68.5
48.6
74.4
29.2
61.6
61.6
65.8
47.4
71.2
28.2
59.3
59.3
62.9
46.2
67.8
27.2
3675
80
70.2
70.2
71.7
65.7
78.3
46.7
68.0
68.0
69.1
64.6
75.4
45.7
65.6
65.6
66.4
63.5
72.4
44.8
63.1
63.1
63.6
62.3
69.2
43.7
85
74.4
74.4
74.4
74.4
78.6
61.9
72.1
72.1
72.1
72.1
75.7
60.8
69.7
69.7
69.7
69.7
72.8
59.8
67.1
67.1
67.1
67.1
69.6
58.6
90
78.6
78.6
78.7
78.7
79.3
78.0
76.2
76.2
76.3
76.3
76.3
76.3
73.7
73.7
73.8
73.8
73.8
73.8
71.0
71.0
71.1
71.1
71.1
71.1
75
67.1
67.1
71.7
51.4
77.8
30.7
64.9
64.9
69.1
50.3
74.7
29.7
62.6
62.6
66.3
49.1
71.5
28.7
60.2
60.2
63.3
47.8
68.0
27.6
4000
80
71.4
71.4
72.3
68.6
78.8
48.3
69.1
69.1
69.8
67.5
75.9
47.4
66.7
66.7
67.1
66.4
72.9
46.4
64.1
64.1
64.2
64.2
69.6
45.4
85
75.6
75.6
75.7
75.7
79.1
64.5
73.3
73.3
73.3
73.3
76.2
63.5
70.8
70.8
70.9
70.9
73.3
62.4
68.1
68.1
68.2
68.2
70.1
61.2
90
79.9
79.9
80.0
80.0
80.1
80.1
77.5
77.5
77.6
77.6
77.6
77.6
74.9
74.9
75.0
75.0
75.0
75.0
72.1
72.1
72.2
72.2
72.3
72.3
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-8 — Gross Cooling Capacities (kW) - Single Compressor - TTA100C Condensing Unit with TWE100A Air Handler
(SI)
Ambient Temperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Entering Wet Bulb (°C)
m
3
/h
Bulb
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
24
18.7
18.3
20.4
13.5
22.3
8.7
18.0
18.0
19.7
13.2
21.5
8.4
17.3
17.3
18.9
12.8
20.6
8.1
16.7
16.7
18.1
12.5
19.7
7.8
5139
27
19.7
19.7
20.5
17.4
22.5
12.6
19.1
19.1
19.8
17.1
21.7
12.2
18.5
18.5
19.0
16.8
20.8
11.9
17.8
17.8
18.2
16.5
19.9
11.9
29
20.9
20.9
20.9
20.9
22.6
16.5
20.2
20.2
20.3
20.3
21.8
16.2
19.6
19.6
19.6
19.6
20.9
15.9
18.9
18.9
18.9
18.9
20.0
15.6
32
22.0
22.0
22.1
22.1
22.7
20.5
21.4
21.4
21.4
21.4
21.9
20.2
20.7
20.7
20.7
20.7
21.1
19.9
20.0
20.0
20.0
20.0
20.2
19.6
24
19.0
19.0
20.7
14.2
22.5
8.7
18.4
18.4
19.9
13.7
21.7
8.4
17.7
17.7
19.1
13.4
20.7
8.1
17.0
17.0
18.3
13.0
19.8
7.8
5692
27
20.2
20.2
20.8
18.3
22.7
13.2
19.5
19.5
20.0
18.0
21.9
12.9
18.9
18.9
19.3
17.7
21.1
12.6
18.2
18.2
18.4
17.4
20.1
12.3
29
21.3
21.3
21.4
21.4
22.8
17.3
20.7
20.7
20.7
20.7
22.0
17.0
20.0
20.0
20.0
20.0
21.1
16.7
19.3
19.3
19.3
19.3
20.2
16.4
32
22.6
22.6
22.6
22.6
23.0
21.7
21.9
21.9
21.9
21.9
22.2
21.4
21.2
21.2
21.2
21.2
21.4
21.1
20.4
20.4
20.4
20.4
20.4
20.4
24
19.3
19.3
20.8
14.5
22.7
8.8
18.7
18.7
20.1
14.2
21.8
8.6
18.0
18.0
19.3
13.9
20.8
8.3
17.3
17.3
18.4
13.5
19.8
8.0
6244
27
20.5
20.5
21.0
19.2
22.9
13.7
19.9
19.9
20.2
18.9
22.1
13.4
19.2
19.2
19.5
18.6
21.2
13.1
18.5
18.5
18.6
18.3
20.3
12.8
29
21.8
21.8
21.8
21.8
23.0
18.1
21.1
21.1
21.1
21.1
22.2
17.8
20.4
20.4
20.4
20.4
21.3
17.5
19.6
19.6
19.7
19.7
20.4
17.2
32
23.0
23.0
23.0
23.0
23.2
22.8
22.3
22.3
22.3
22.3
22.4
22.4
21.6
21.6
21.6
21.6
21.6
21.6
20.8
20.8
20.8
20.8
20.8
20.8
24
19.7
19.7
21.0
15.1
22.8
9.0
19.0
19.0
20.2
14.7
21.9
8.7
18.3
18.3
19.4
14.4
20.9
8.4
17.6
17.6
18.5
14.0
19.9
8.1
6796
27
20.9
20.9
21.2
20.1
23.1
14.2
20.2
20.2
20.4
19.8
22.2
13.9
19.5
19.5
19.7
19.5
21.3
13.6
18.8
18.8
18.8
18.8
20.4
13.3
29
22.1
22.1
22.2
22.2
23.2
18.9
21.5
21.5
21.5
21.5
22.3
18.6
20.7
20.7
20.7
20.7
21.5
18.3
19.9
19.9
20.0
20.0
20.5
17.9
32
23.4
23.4
23.4
23.4
23.4
23.4
22.7
22.7
22.7
22.7
22.7
22.7
21.9
21.9
22.0
22.0
22.0
22.0
21.1
21.1
21.1
21.1
21.2
21.2
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity